- 11 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Refrigeration Cycle Diagram
Heat Pump
ORIFICE
(Capillary only
for 60k Btu)
ORIFICE
(Only for
60k Btu)
HP
• If 60K Model is installed at a distance of 15m, 525g of refrigerant should be added
(15-7.5) x 70g = 525g
30k Btu/h
5/8"
3/8"
7.5
30
5
15
70
36k Btu/h
5/8"
3/8"
7.5
30
5
15
50
42k Btu/h
3/4''
3/8"
7.5
30
5
15
70
48k Btu/h
3/4''
3/8"
7.5
30
5
15
70
60k Btu/h
3/4''
3/8"
7.5
30
5
15
70
72k Btu/h
1''
1/2"
7.5
25
5
20
70
90k Btu/h
9/8''
5/8"
7.5
30
5
20
90
100k Btu/h
9/8''
5/8"
7.5
30
5
20
100
Capacity
Gas
Liquid
Elevation B(m)
Piping Length
A(m)
* Additional
Refrigerant
(g/m)
Pipe Size (Diam-
eter: Ø)
inch
Standard
Standard
Max.
Max.
Capacity
Orifice Number
30k
63
36k
62
42k
74/72
48k
86/90
72k
98
90k
84
100k
104
Orifice Number
Содержание LBNH608RSS1