Installation Manual  15

ENGLISH

Installation of Indoor, Outdoor Unit

INSTALLATION OF REMOTE CONTROL BOX

Install the remote control box and
cord correctly.

• Although the room temperature sensor is in the indoor unit, the remote control box should

be installed in such places away from direct sunlight and high humidity.

INSTALLATION OF THE REMOTE CONTROL BOX

• Select places that is not splashed by

water.

• Select control position after receiving

customer approval.

• The room temperature sensor of the

thermostat for temperature control is built
in the indoor unit.

• This remote controller equipped with liquid

crystal display. If this position is higher or
lower, display is difficult to see.
(The standard height is 1.2~1.5m high)

ROUTING OF THE REMOTE CONTROL CORD

• Keep the remote control cord away from

the refrigerant piping and the drain piping.

• To protect the remote control cord from

electrical noise, place the cord at least
5cm away from other power cables. (Audio
equipment, Television set, etc)

• If the remote control cord is secured to a

wall, provide a trap at the top of the cord to
prevent water droplets from running.

POINT OF REMOTE CONTROLLER INSTALLATION

DISASSEMBLING OF THE REMOTE CONTROLLER

ELECTRICAL WIRING TO THE INDOOR UNIT

 

Make sure that wire and terminal
numbers are matched on unit side 
and remote controller side.

(Main board)

CN REMO

The maximum length of the cord is 100m. 

If the length of the cord exceeds 50m, use a wire size greater than 0.5mm

2

.

Remote controller

CN REMO

Remote

control 

box body

Lever carefully 

the box open 

using a screw 

driver, etc.

Front case

The lower part

Face of wall

Upper notch

Upper flange

Under plate

Remote

control cord

Remote

control unit

Tapping screw

(Local supply)

Lower notch

Face of wall
Upper notch

Lower notch
Switch box

(Local supply)

Under plate
Remote

control unit

Remote

control cord

Screw

(Local supply)

Cord

clamp

Push hand

(Part B)

(Part A)

FIXING OF REMOTE 
CONTROL CORD
1. Fix the cord clamps on the wall 

by ø3 tapping screws(Local supply).

2. Fix the remote control cord.

PROCEDURE OF INSTALLATION
1. Fix the under plate on the switch box by

screws(Local supply). In this case, fit the under
plate on the wall, and be careful of deformation.

2. Receive the remote control cord in the switch box.
3. Hook the remote control unit on the under plate.

WHEN THE REMOTE CONTROL BOX IS

INSTALLED WITH THE CORD BURIED.

PROCEDURE OF INSTALLATION
1. Fix the under plate on the wall by self tapping

screws (accessory).

2. Make a slit (Part A) at the top side of the remote

control box by nipper.

3.Rout the cord as shown in the following figure. In

this case, push the cord into the around of
case(Part B).

4. Hook the remote control unit on the under plate.

WHEN THE REMOTE CONTROL BOX IS
INSTALLED WITH THE CORD EXPOSED.

Содержание LB-H60BESA0

Страница 1: ...etely before installing the product When the power cord is damaged replacement work shall be performed by authorized personnel only Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly ...

Страница 2: ...door Unit and Outdoor Unit 22 Air Purging of the Connecting Pipes and the Indoor Unit 25 Group Control 26 Two Thermistor system 26 Static Pressures Air Flow Rate 27 Installation Requirements Required Parts Required Tools Four Type A screws Connecting cable Level Screw driver Electric drill Hole core drill ø70mm Pipes Gas side 1 2 5 8 3 4 Liquid side 1 4 3 8 1 2 Insulated drain hose Insulation mate...

Страница 3: ...ndicates the possibility of injury or damage to properties only Installation Be sure not to do Be sure to follow the instruction Do not use a defective or underrated circuit breaker Use this appliance on a dedicated circuit There is risk of fire or electric shock For electrical work contact the dealer seller a qualified electrician or an Authorized Service Center Do not disassemble or repair the p...

Страница 4: ...e to the product Be sure the installation area does not deteriorate with age If the base collapses the air conditioner could fall with it causing property damage product failure and personal injury Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open Moisture may condense and wet or damage furniture Take care to ensure that power cab...

Страница 5: ...he product on Do not use the telephone or turn switches on or off There is risk of explosion or fire If strange sounds or small or smoke comes from product Turn the breaker off or disconnect the power supply cable There is risk of electric shock or fire Stop operation and close the window in storm or hurricane If possible remove the product from the window before the hurricane arrives There is ris...

Страница 6: ...product where it will be exposed to sea wind salt spray directly It may cause corrosion on the product Corrosion particularly on the condenser and evaporator fins could cause product malfunction or inefficient operation When the product is not be used for a long time disconnect the power supply plug or turn off the breaker There is risk of product damage or failure or unintended operation Take car...

Страница 7: ...tion or damage Do not insert hands or other objects through the air inlet or outlet while the product is operated There are sharp and moving parts that could cause personal injury Do not drink the water drained from the product It is not sanitary and could cause serious health issues Use a firm stool or ladder when cleaning or maintaining the product Be careful and avoid personal injury Replace th...

Страница 8: ...Controller Side Rear Air intake vents Air outlet vents Piping Drain hose Connecting wire Control cover This symbol alerts you to the risk of electric shock This symbol alerts you to hazards that could cause harm to the air conditioner This symbol indicates special notes NOTICE Introduction Symbols Used in this Manual Features ...

Страница 9: ...ith the outdoor unit The place where the unit is not affected by an electrical noise The place where air circulation in the room will be good There should not be any heat source or steam near the unit Outdoor unit If an awning is built over the unit to prevent direct sunlight or rain exposure be careful that heat radiation from the condenser is not restricted There should not be any animals or pla...

Страница 10: ...3 4 Liquid 1 2 Elevation B m Length A m Additional refrigerant g m Pipe Size Diameter Ø Standard 7 5 Standard 5 Max 50 Max 30 60k Btu h 3ø CAUTION If 60k Model is installed at a distance of 50m 3612 5g of refrigerant should be added 50 7 5 x 85g 3612 5g Capacity is based on standard length and maximun allowance length is on the basis of reliability Improper refrigerant charge may result in abnorma...

Страница 11: ...as a figure for easy water drainage A place where the unit will be leveled and that can support the weight of the unit A place where the unit can withstand its vibration A place where service can be easily performed CASE 1 POSITION OF SUSPENSION BOLT Drainage hole A B C 1 3 mm D G H I E F M10 Nut M10 SP washer M10 washer X 4 X 4 Local supply X 4 M10 Nut M10 SP washer M10 washer X 4 X 4 Local suppl...

Страница 12: ...washer onto the suspension bolts for locking the suspension bolts on the ceiling Mount the suspension bolts to the set anchor firmly Secure the installation plates onto the suspension bolts adjust level roughly using nuts washers and spring washers CAUTION Tighten the nut and bolt to prevent unit falling 1 Set anchor Old building New building 2 Plate washer 3 Spring washer 4 Nut 5 Suspension bolts...

Страница 13: ...lways lay the drain with downward inclination 1 50 to 1 100 Prevent any upward flow or reverse flow in any part 5mm or thicker formed thermal insulator shall always be provided for the drain pipe Install the P Trap or U Trap to prevent a water leakage caused by the blocking of intake air filter Applied U Trap Dimension 1 Install declination of the indoor unit is very important for the drain of the...

Страница 14: ...ood Drain Is the drainage smoothly and no sweating Gas leakage Is the piping connection correctly Wiring Is the wiring connection correctly Lock bolt Is the lock bolt of compressor loosened THERMAL INSULATION TEST AND CHECK Make sure that there is no clearance here Overlap with thermal insulator for piping Thermal insulator for refrigerant pipe Local supply Thermal insulator for piping Local suppl...

Страница 15: ...mbers are matched on unit side and remote controller side Main board CN REMO The maximum length of the cord is 100m If the length of the cord exceeds 50m use a wire size greater than 0 5mm2 Remote controller CN REMO Remote control box body Lever carefully the box open using a screw driver etc Front case The lower part Face of wall Upper notch Upper flange Under plate Remote control cord Remote con...

Страница 16: ...even segment LED display For proper display of the remote controller LED s the remote controller should be installed properly as shown in Fig 1 The standard height is 1 2 1 5 m from floor level Operation unit ZONE 1 2 3 4 Humidify JET AUTO AUTO SWING OPERATION FAN SPEED Program set SUB FUNCTION SET TEMP Room Temp HI MED LO Heater Defrost Filter Preheat Out door Time Timer On Set no Time Off 01 03 ...

Страница 17: ...tand its vibrations Keep a maintenance space REFRIGERANT PIPING INSTALLATION OF OUT DOOR UNIT Perform the work according to the Service Manual or Installation Guide Select a location that satisfies the following conditions Install the unit firmly in place Use two spanners when connecting the refrigerant pipe to the unit Make a bend with a radius as large as possible Perform air purge with R 22 or ...

Страница 18: ...ove crews Use the cord clamper to fix the cord Perform the electrical wiring work according to the electrical wiring connection All wiring must comply with local requirements Select a power source that is capable of supplying the current required by the air conditioner Use a recognized circuit breaker between the power source and the unit A disconnection device to adequately disconnect all supply ...

Страница 19: ...avoid to let burrs drop in the tubing Putting nut on Remove flare nuts attached to indoor and outdoor units than put them on pipe tube having completed burr removal Not possible to put them on after flaring work Flaring work Carry out flaring work using flaring tool as shown below Firmly hold copper tube in a bar or die as indicated dimension in the table above Check Compare the flared work with f...

Страница 20: ...raight pipes generally using ready made sockets While brazing protect piping against heat with wet cloth to avoid damaging valve packing or burning thermal insulator with burner heat While brazing blow inert gas nitrogen gas or carbonic gas to prevent formation of oxidation film in copper piping otherwise the refrigerant circuit will clog The blowing of nitrogen gas or carbonic gas through 3 way v...

Страница 21: ...wrench until the wrench clicks When tightening the flare nut with torque wrench ensure the direction for tightening follows the arrow on the wrench Checking the Drainage Remove the Air Filter Check the drainage Spray one or two glasses of water upon the evaporator Ensure that water flows drain hose of indoor unit without any leakage Torque wrench Outdoor unit Gas side piping Bigger Dia Liquid side...

Страница 22: ...he middle of live pin on the power plug should be over 1 8m The power cord connected to the outdoor unit should be complied with the following specifications Rubber insulation type H05RN F approved by HAR or SAA If the supply cord is damaged it must be replaced by a special cord or assembly availible from the manufacturer of its service agent The connecting cable connected to the indoor and outdoo...

Страница 23: ...tings are liable to come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could give rise to burn out of the wires 4 Specification of power source 5 Confirm that electrical capacity is sufficient 6 Be sure that the starting voltage is maintained at more than 90 percent of the ra...

Страница 24: ...by taping along the exterior wall and fix it onto the wall by saddle or equivalent Tape the Pipings and Connecting cable from bottom to top Form the pipings gathered by taping along the exterior wall and make the trap prevent water from entering into the room Fix the pipings onto the wall by saddle or equivalent Trap is required to prevent water from entering into electrical parts Seal a small ope...

Страница 25: ... gas leak detector 3 Remove the service port nut and connect the gauge manifold and the vacuum pump to the service port by the charge hose 4 Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below 76cmHg 5 Remove the valve stem nuts and fully open the stems of the 2 way and 3 way valves with a hexagon wrench 6 Tighten the valve stem nuts of the 2 way valve and 3 ...

Страница 26: ...YL SIGNAL BR GND YL SIGNAL BR GND Connecting Cable Local Supply Connector Connector YL SIGNAL BR GND YL SIGNAL BR GND YL SIGNAL BR GND Remote Controller PCB Single Group Slide Switch2 Using the supplied Wired Remote Controller wire them like above Move slide switch 2 to Group position Ensure that the color of wire Open the rear cover of Remote Controller to set up the mode Selectable options are t...

Страница 27: ...ow Rate Hi 55 53 5 53 51 5 51 50 5 49 47 5 LB H60BESA0 Med 46 5 45 44 43 5 42 5 41 5 41 39 5 Lo 39 5 37 5 37 35 5 34 5 34 33 5 32 Static Pressure mmAq Setting Value 0 2 4 6 8 10 12 15 Model Step Table is based at 220V According to the fluctuation of voltage air flow rate varies NOTICE ...

Страница 28: ...P No 3828A20463B ...

Отзывы: