Refrigeration Cycle Diagram
• HEAT PUMP (LB-H1860RH/LB-H2460RH/LB-G3680RH/LB-G3660RH/
LB-G3660PH/LB-E4880RH/LB-E6080RH)
–13–
INDOOR UNIT
OUTDOOR UNIT
HEAT
EXCHANGER
HEAT
EXCHANGER
COMPRESSOR
GAS SIDE
LIQUID SIDE
COOLING
HEATING
REVERSING
VALVE
CAPILLARY TUBE
• Rated performance for refrigerant line length of: 7.5m
• If 18K Model is installed at a distance of 15m, 255g of refrigerant should be added (15-7.5)x30g=225g
LB-H1860RH
5/8"
1/4"
7.5
50
5
30
30
LB-H2460RH
5/8"
1/4"
7.5
50
5
30
30
LB-G3660RH/PH
5/8"
1/4"
7.5
50
5
30
40
LB-G3680RH
5/8"
1/4"
7.5
50
5
30
40
LB-E4880RH
3/4"
3/8"
7.5
50
5
30
40
LB-E6080RH
3/4"
1/2"
7.5
50
5
30
80
Pipe size(Diameter: ø)
Piping length(m)
Elevation(m)
MODEL
Gas
Liquid
Rated
Max.
Rated
Max.
*Additional
refrigerant
(g/m)