50 MPS Multi Air Conditioner
Installation
Connection method of the connecting
cable(Example)
(1) Dismount two-caps on the conduit panel.
(2) Make a hole appropriate for the passage of connec-
tion cable through on cap by tool.
(for low voltage line)
(3) Pass the connecting cable through the hole.
(4) Properly connect the cable on the terminal block.
(5) Fix the connection cable with clamp cord provided on
the unit not to have strain at the terminal when the
connection cable is pulled outside up to a 35 pound
weight.
(6) Wind the vinyl tape round the connecting cable for
sealing between the surface of the connection cable
and cap.
(7) Mount the taped part of cable on the cap.
(8) Finally, mount the holed cap with the wound cable on
the conduit panel.
When connecting each power wire to the corresponding
terminal, follow instructions "How to connect wiring to the
terminals" and fasten the wire tightly with the fixing screw
of the terminal plate.
How to connect wiring to the terminals
For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter of wire-cutting pli-
ers, then strip the insulation to expose the solid wire
about 25mm(15/16")
(2) Using a screwdriver, remove the terminal screw(s) on
the terminal plate.
(3) Using pliers, bend the solid wire to from a loop suit-
able for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal
plater and tighten securely with the terminal screw
using a screwdriver.
For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pli-
ers, then strip the insulation to expose the strand
wiring about 10mm(3/8").
(2) Using a screwdriver, remove the terminal screw(s) on
the terminal plate.
(3) Using a round terminal fastener or pliers, securely
clamp each stripped wire end with a round terminal.
(4) Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
Loose wiring may cause the terminal to overheat or
result in unit malfunction. A fire hazard may also exist.
Therefore, be sure all wiring is tightly connected.
WARNING
G
Terminal
block
Lock nut
Power supply line
(1ø, 230/208V)
Conduit panel
Cap(Reuse)
Clamp cord
Hole
(for low voltage line)
Cap(Remove)
Taping
(for sealing)
Low voltage line
(connecting cable)
Loop
Str
ip 25mm(15/16")
Insulation
Solid wire
High voltage
Low voltage
Str
ip 10mm(3/8")
Round
terminal
Connecting cable
Loosening the
terminal block
screw
Fastening the
wire tightly
Strand wire