Chapter 2. SPECIFICATIONS
2 - 1
Chapter 2 . SPECIFICATIONS
Table 2.1 shows the general specifications of MASTER-K series.
No
Items
Specifications
Standard
1
Operating ambient
temperature
0 ~ 55
2
Storage ambient
temperature
-25 ~ 70
3
Operating ambient
humidity
5 ~ 95%RH, non-condensing
4
Storage ambient
humidity
5 ~ 95%RH, non-condensing
Occasional vibration
Frequency
Acceleration
Amplitude
Sweep count
10
f
57 Hz
-
0.075 mm
57
f
150 Hz
9.8
{1G}
-
Continuous vibration
Frequency
Acceleration
Amplitude
10
f
57 Hz
-
0.035 mm
5
Vibration
57
f
150 Hz 4.9
{0.5G}
-
10 times in each
direction for
X, Y, Z
IEC 1131-2
6
Shocks
*Maximum shock acceleration: 147
{15G}
*Duration time :11 ms
*Pulse wave: half sine wave pulse( 3 times in each of X, Y and Z directions )
IEC 1131-2
Square wave impulse noise
1,500 V
Electrostatic discharge
Voltage :4kV(contact discharge)
IEC 1131-2
IEC 801-2
Radiated electromagnetic field
27 ~ 500 MHz, 10 V/m
IEC 1131-2
IEC 801-3
Severity
Level
All power
modules
Digital
I/Os
( Ue
≥
24 V)
Digital I/Os
(Ue
<
24 V)
Analog I/Os
communication
I/Os
7
Noise immunity
Fast transient burst noise
Voltage
2 kV
1 kV
0.25 kV
IEC 1131-2
IEC 801-4
8 Operating atmosphere
Free from corrosive gases and excessive dust
9
Altitude for use
Up to 2,000m
10
Pollution degree
2 or lower
11
Cooling method
Self-cooling
[Table 2.1 ] General specifications
REMARK
1) IEC(International Electrotechnical Commission)
: The international civilian organization which produces standards for electrical and electronics industry.
2) Pollution degree
: It indicates a standard of operating ambient pollution level.
The pollution degree 2 means the condition in which normally, only non-conductive pollution occurs.
Occasionally, however, a temporary conductivity caused by condensation shall be expected.
2.1 General Specifications