14
Instructions for the installer
5.3 Regulation for natural gas
The hob has been adjusted for
natural gas
at a pressure of
1.0kPa. To allow the unit to work with this type of gas, perform the
same operations described in paragraph “5.2 Regulation for ULPG”,
but choose the nozzles and regulate the primary air for natural gas,
as shown in the following table and in paragraph “5.4 Regulation of
primary air”. After the regulations have been carried out, restore the
seals with sealing wax or equivalent material.
NG
– 1.0 kPa
Burner (*)
Nominal gas
Injector
consumption (mm)
(MJ/h)
Auxiliary (1)
4.8
0.98
Semi rapid (2)
6.0
1.10
Rapid (3)
9.0
13.5
Wok (4)
15.0
1.70
5.4 Regulation of primary air
Referred to distance “X” in mm.
BURNER
NG
– 1.0 kPa
ULPG
– 2.75 kPa
Auxiliary (1)
2
2
Semi-rapid (2)
3.0
3.0
Average rapid (3)
3.5
3.5
Wok (4)
8
8.0
To identify the burners on your hob, refer to the drawings in point
“6.3 Arrangement of burners on hob”