Chapter 5. GM PROGRAMMING
5 -10
7.3 Programming for Loading the A/D Conversion Module
on Remote I /O Station
1) System Configuration
2) Initial Settings
(1) A/D conversion enabling channel: channel 0
(2) Conversion data range: -192 to 16191
(3)Time average processing channel: channel 0(setting value: 1,000 ms)
3) Descriptions of the Program
(1)The digital value less than 8000of channel 0 turns %Q0.1.0 on.
(2)The digital value more than 8000 or same, and less than 10,000 or same of channel 0 turns %Q0.1.1 on.
(3)The digital value more than 10,000 or same, and less than 12,000 of channel 0 turns %Q0.1.2 on.
(4)The digital value more than 12,000 or same of channel 0 turns %Q0.1.3 on.
Remote
Station No. “1”