Chapter 8 MK Programming
8 - 5
8.2.2 Output the analog input value by 7-segment display
1) System configuration
(A/D module is mounted on slot 2)
2) Initial setting for A/D module
No
Item
Setting
Buffer memory
address
Data to be
written
1
Channel to be used
Ch 0
0
h0001
2
Analog input type and range
DC4~20mA
1
h0000
3
Averaging processing enable
Ch 0
2
h0001
4
Averaging count
Ch 0 : 10 times
3
h000A
5
Validate setting
7
h0001
3) Description of program
①
When the P0000 is on, initialize the A/D module.
②
When the P0001 is on, read the digital value of channel 0 from buffer memory of A/D
module and store it into the D0008.
③
When the P0002 is on, output the contents of D0008 to the 7 -segment display.
GM6-
PAFB
K3P-
07AS
G6I-
D22A
G6Q-
TR2A
G6F-
AD2A
P000
P001
P002
P0000
P0001
P0002
Initialize A/D module
Read digital value
Output digital value to
BCD display
Channel 0 : Analog input (DC4 ~ 20mA
7-segment display