5. Trouble Shooting
- 121 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
22
Max. C/T
Input Over Current
1. Malfunction of Compressor
2. Blocking of Pipe
3. Low Voltage Input
4. Refrigerant, Pipe length, Blocked...
Display
code
Title
Cause of error
Check point & Normal condition
■
Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
No
Yes
Yes
Yes
Recheck power and installation condition
Yes
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
→
Reassemble or manage if abnormality found
Is inverter PCB assembly
power connection normal?
No
Check connection between inverter PCB assembly and
bridge diode(misconnection, disconnection)
→
wiring again if abnormality found
Yes
Is input voltage normal?
No
Check
R~S/S~T/T~R phase voltage is 380V
±
10%
R~N/S~N/T~N phase voltage is 220V
±
10%
→
Check connection condition and wiring if power is
abnormal.
Yes
Is inverter PCB assembly
normal?
No
Check inverter PCB assembly IPM normality
→
Replace inverter PCB assembly
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
1. Check resistance between each terminal of compressor
1.083~1.123
Ω
±
5%
2. Check insulation resistance between compressor
terminal and pipe (over 50M
Ω
)
→
Replace compressor if abnormality found
Is compressor
Wire connection
condition normal?
No
1. Check inverter PCB assembly U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
→
Reassemble if abnormality found