5. Wiring Connection
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
[Air inlet side view]
The power cord connected to the outdoor unit
should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR
or SAA).
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications (Rubber insulation, type H05RN-F
approved by HAR or SAA).
CAUTION
8.5mm
20mm
GN/YL
7.5mm
20mm
GN/YL
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
(18K/24K/28K/36K)
1.25mm
2
(48K)
NORMAL
CROSS-SECTIONAL
AREA 2.5mm
2
(18K/24K/28K/36K)
3.5mm
2
(48K)
Control box cover
Indoor
power cord
Remote
controller
cord
Control box cover
Terminal Block of Outdoor Unit
1(L) 2(N) 3
4
5
1(L) 2(N) 3
4
5
Terminal Block of Outdoor Unit
1(L) 2(N) 3
4
5
Terminal Block of Indoor Unit
Terminal Block of Indoor Unit
POWER INPUT
R
S
T
N
POWER INPUT
R
S
T
N
1(L) 2(N) 3
4
5
Terminal Block of Indoor Unit
3(L) 4(N)
5
6
7
1(L) 2(N)
3(L) 4(N)
5
6
7
8
Terminal Block of Outdoor Unit
Power Cord
Terminal Block of Indoor Unit
3(L) 4(N)
5
6
7
1(L) 2(N)
3(L) 4(N)
5
6
Terminal Block of Outdoor Unit
Power Cord
■
18K/24K/28K Btu
■
36K/48K Btu
• Heat Pump Model
• Cooling Model
• Heat Pump Model
• Cooling Model
Make sure that the screws of the terminal are free from looseness.
WARNING
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer
or its service agent.
8