Appendix 3
80
BACnet Gateway
Appendix 3
BACnet Gateway Error Response Table
• Error PDU
Error PDU
Error Code
Error Class
Device(0)
Configuration_In_Progress(2)
Object(1)
Unknown_Object(31)
Property(2)
Unknown_Property(32)
Property(2)
Write_Access_Denied(40)
Property(2)
Invalid_Datatype(9)
Property(2)
Invalid_Array_Index(42)
Property(2)
Value_Out_Of_Range(37)
Resource(3)
Other(0)
Resource(3)
No_Space_To_Add_List_Element(19)
Service(5)
Other(0)
Service(5)
Property_Is_Not_List(22)
Reading of the object list during the initialization of
the LG-NET
Request to access to an object not installed.
Request to access to a property not installed.
Request to write to a prohibited area.
Request to write in a format different from the
property.
Request to access to a specified index outside the
array index range.
Request to write a value outside the permissible
range.
A COV registration request of more than 10
registration items.
An Event registration request of more than 10
registration items.
Request for the deletion of an element not existing in
the list.
Request for the execution of the
AddListElement/RemoveListElement for a property
that is not of List type.
• Reject PDU
Reject PDU
Reject Reason
Inconsistent_Parameter(2)
Invalid_Parameter_Data_Type(3)
Invalid_Tag(4)
Missing_Required_Parameter(5)
Too_Many_Arguments(7)
Unrecognized_Service(9)
A propertyID or value overflow or underflow occurred during
WritePropertyMultiple operation.
The type of parameter for the execution of the service is different in
type.
An error was detected during tag decoding.
A parameter shortage occurred during the execution of the service.
Too many arguments for the execution of the service.
An attempt to execute an unsupported service with confirmation.
• Abort PDU
Abort PDU
Abort Reason
Buffer_Overflow(1)
Invalid_APDU_In_This_State(2)
Segmentation_Not_Supported(4)
Unable to process due to too many requests beyond the capacity.
The processing of segments was aborted because an expected APDU
was received.
The response side does not support the segment.