- 3 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Specification
Note:
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Heating Temperature : Indoor 20°C(68°F) DB / 15°C(59°F) WB
Outdoor 7°C(44.6°F) DB / 6°C(42.8°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased(maximum 3dB(A)) owing to ambient conditions during operation.
Outdoor unit
AVUQ30GLLA1
AVUQ36GLLA1
Power Supply
V , Ø , Hz
220-240 / 1 / 50
220-240 / 1 / 50
Starting Current
Cooling
Max.
A
-
-
Heating
Max.
A
-
-
Wiring Connections
Power Supply Cable (included Earth)
No. x mm
2
(AWG)
3C x 2.5
3C x 5.0
Casing Color
-
Warm Gray
Warm Gray
Dimensions
W x H x D
mm
950 × 834 × 330
950 × 834 × 330
W x H x D
inch
37-13/32 x 32-27/32 x 13
37-13/32 x 32-27/32 x 13
Net Weight
kg (lbs)
60 (132.3)
60 (132.3)
Compressor
Type
-
Twin Rotary
Twin Rotary
Model
Model x No.
GJT240MAA x 1
GPT442MAB x 1
Motor type
-
BLDC
BLDC
Motor Output
W x No.
2,137 x 1
2,137 x 1
Refrigerant
Type
-
R410A
R410A
Precharged Amount
g (oz)
1,700
2,050
Chargeless-Pipe Length
m (ft)
7.5 (24.6)
7.5 (24.6)
Additional Charging Volume
g/m (oz/ft)
40 (0.43)
40 (0.43)
Control
-
Electronic Expansion Valve
Electronic Expansion Valve
Refrigerant Oil
Type
-
FVC68D
FVC68D
Charged volume
cc x No.
900 x 1
1,300 x 1
Heat Exchanger
(Row x Column x Fins per inch) x No.
-
(2 x 40 x 21) x 1
(2 x 40 x 21) x 1
Fan
Type
-
Propeller
Propeller
Air Flow Rate
m
3
/min x No.
58 x 1
60 x 1
Fan Motor
Type
BLDC
BLDC
Output
W x No.
137 x 1
137 x 1
Sound Pressure Level
Cooling
Rated
dB(A)
55
55
Heating
Rated
dB(A)
-
-
Sound Power Level
Cooling
Rated
dB(A)
-
-
Piping Connections
Liquid
Outer Dia.
mm(inch)
Ø 9.52 (3/8)
Ø 9.52 (3/8)
Gas
Outer Dia.
mm(inch)
Ø 15.88 (5/8)
Ø 15.88 (5/8)
Piping Length
Max.
m (ft)
50 (164.0)
50 (164.0)
Maximum Height Difference
Outdoor Unit ~ Indoor Unit
Max.
m (ft)
30 (98.4)
30 (98.4)
Operation Range
(Outdoor Temperature)
Cooling
Min. ~ Max.
DB ( DB)
-15 (5.0) ~ 48 (118.4)
-15 (5.0) ~ 48 (118.4)
Heating
Min. ~ Max.
WB ( WB)
-
-
°C °F
°C °F
Содержание AV-Q30GLLA1
Страница 12: ...P NO MFL51168428 OCTOBER 2013 ...