WIRING CONNECTION
11
ENGLISH
Connecting Cables between Indoor Unit and Outdoor Unit
Outdoor
unit
Indoor
unit
1
2
3
1
2
3
The power cord connected to the outdoor unit should be complied with IEC 60245 or HD
22.4 S4 (This equipment shall be provided with a cord set complying with the national
regulation.
The connecting cable connected to the outdoor unit should be complied with IEC 60245 or
HD 22.4 S4 (This equipment shall be provided with a cord set complying with the national
regulation.)
If the supply cord is damaged, it must be replaced by a special cord or assembly available
from the manufacturer of its service agent.
When the connection line between the indoor unit and
outdoor unit is over 40 m, connect the telecommunication line
and power line separately.
CAUTION
!
GN/
YL
20 m
m
35±5 mm
10±3 mm
NORMAL
CROSS-SECTIONAL
AREA 0.75 mm
2
20 mm
GN
/Y
L
35±
5 mm
10±3 mm
Chassis
Phase(Ø)
Area(mm
2
)
UL2 : 18 kBtu/h
U24A : 24 kBtu/h
U4 : 36 kBtu/h
1
2.5
U4 : 48 kBtu/h
U3 : 54 kBtu/h
U3 : 50 kBtu/h
U5 : 54 kBtu/h
1
6