Ceiling Cassette Air Conditioner
Installation
The power cord connected to the outdoor unit
should be complied with the following specifications
(Rubber insulation, type H07RN-F approved by HAR
or SAA).
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer
or its service agent.
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications (Rubber insulation, type H05RN-F
approved by HAR or SAA).
CAUTION
20mm
GN/YL
20mm
GN/YL
NORMAL
CROSS-SECTIONAL
Capacity
A(mm)
24k/30k 2.5mm
42k/48k
2.5mm
Capacity
A(mm)
24k/30k
42k/48k
0.75mm
1mm
Wiring Connection
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
1 Phase
24k/30k
Remote Controller
Cable
Connecting
Cable
3 Phase
42k/48k
1(L) 2(N) 3
1(L) 2(N)
1(L) 2(N)
3
Outdoor Unit
Indoor Unit
Main Power
1Ø, 220V
1(L) 2(N) 3
1(L) 2(N)
R
S
T
N
3
Outdoor Unit
Indoor Unit
Main Power
3Ø, 380V
Electricwire
Round crimp-style terminal
Attach insulation sleeve
Connect wires of the same gauge to both sides
WARNING: Make sure that the screws of the terminal are free from
looseness.