- 49 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
■
Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
Self-diagnosis Function
Indoor Error
Error code
Description
INV TPS
LED 1
(Red)
LED 2
(Green)
Indoor
Status
00
No Error
ON
01
Indoor Room themistor error
1time
OFF
02
Indoor in-piping sensor error
2times
OFF
05
Communcation error between in and out
5times
OFF
06
Indoor Out-Piping sensor error
6times
OFF
Outdoor Error
Error Code
Description
INV TPS
LED 1
(Red)
LED 2
(Green)
Indoor
Status
21
DC Peak (IPM Fault)
2times
1time
OFF
22
CT 2(Max CT)
2times
2times
OFF
23
DC Link Low Volt.
2times
3times
OFF
24
L_P/Heater Sink
2times
4times
OFF
25
Low voltage / Over voltage
2times
5times
OFF
26
DC Comp Position Error
2times
6times
OFF
27
PSC Fault Error
2times
7times
OFF
28
DC Link High Volt
2times
8times
OFF
32
D-Pipe High (INV)
3times
2times
OFF
33
D-Pipe High (Normal)
3times
3times
OFF
40
CT Sensor (Open/Short)
4times
O
OFF
41
INV. D-PipeTh Error(Open/Short)
4times
1time
OFF
44
Outdoor air Th Error(Open/Short)
4times
4times
OFF
45
Cond. Pipe Th Error(Open/Short)
4times
5times
OFF
46
Suction Pipe Error(Open/Short)
4times
6times
OFF
47
Const D-pipe Th Error(Open/Short)
4times
7times
OFF
51
Capacity over
5times
1time
OFF
53
Signal error (Indoor
↔
Outdoor)
5times
3times
OFF
60
EEPROM Check Sum Error
6times
O
OFF
61
Cond. Pipe High
6times
1time
OFF
62
Heatsink High
6times
2times
OFF
63
Cond. Pipe Low
6times
3times
OFF
65
Heatsoml Th error (Open/Short)
6times
5times
OFF
Содержание AS-W2465DH0