Operation
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed from
starting of heating operation and more than 4 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature
rises over 15°C even before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed
from ending of the first defrost and more than 4 minutes operation of compressor.
Defrost Control(Heating)
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation(cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated super-high speed for 30 min. at cooling mode operation.
• In the Jet Cool mode, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode input while the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vane is reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet cool mode operation
On-Timer Operation
Off-Timer Operation
Off-Timer <=> On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.