Troubleshooting Guide
10
• D_pipe TH. is short or open
• D_pipe TH. is not connected to the outdoor pcb assembly
• Damage or defect on the sensing circuit of outdoor pcb assembly
D-Pipe TH. is short or
open
D_PIPE TH. is connected to
Outdoor pcb assembly ?
D_PIPE TH. is right ?
YES
No
Connect to CN-D_PIPE
in outdoor pcb assembly
Sensing circuit of outdoor
pcb is right ?
No
Check D_PIPE TH.
- Measure resistance of TH.
(about 200k
Ω
at 25
°
C.)
YES
No
- Check soldering state of
R07H, R08H, C04H
Check flow
Description
Cause of error
Error code