Installation Manual
43
Electrical Wiring
Example Connection of Communication Cable
1. 3Ø, 50Hz
◆
Example Connection of Communication Cable
■
ARUN40LH2A, ARUN50LH2A, ARUN60LH2A
3 Phase 4 Wires
Power supply
50Hz 380~415V
Power supply
1 Phase 50Hz
220~240V
3 Phase 4 Wires Power line(R, S, T, N)
Single Phase of power supply line(L, N)
Communication line (3 line): Wired remote control
Communication line (2 shield line): Between Indoor Unit and Outdoor Unit
Power supply switch
(Switch fuse : ELCB)
Power supply switch
(Switch fuse)
Between Indoor and Outdoor unit
(Main Switch)
IDU
SODU
DRY1 DRY2 GND
INTERNET
B
A
B
A
12V
B
A
3
4
3
4
3
4
Pull Box(Installer Option)
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system
consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and
off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.