32
ENGLISH
Display
Title
Cause of Error
3
2
3
4
3
5
3
6
4
0
4
1
4
2
4
3
4
4
4
5
4
6
5
1
5
3
6
0
6
7
7
3
1 1 3
1 1 5
1 5 1
2 4 2
Outdoor unit related error
Outdoor Unit Inverter Compressor High Discharge
Temperature
High Pressure of Outdoor Unit
Low Pressure of Outdoor Unit
Low pressure ratio
Outdoor Unit Inverter Compressor CT Sensor Fault
Outdoor Unit Inverter Compressor Discharge Temper-
ature Sensor Fault
Outdoor Unit Low Pressure Sensor Fault
Outdoor Unit High Pressure Sensor Fault
Outdoor Unit Air Temperature Sensor Fault
Outdoor Unit Heat Exchanger Temperature Sensor
Fault
Outdoor Unit Suction Temperature Sensor Fault
Excessive capacity of indoor units
Communication error : indoor unit
→
main PCB of out-
door unit
Inverter PCB EEPROM error
Outdoor Unit Fan Lock
Instant Over Current(Peak) of Outdoor Unit PFC
Outdoor Unit Liquid pipe Temperature Sensor Error
Outdoor Unit Subcooling Outlet Temperature Sensor
Error
Failure of operation mode conversion at Outdoor Unit
Network error
System is turned off by outdoor unit Inverter Compressor High Dis-
charge Temperature
System is turned off by excessive increase of high pressure of out-
door unit
System is turned off by excessive decrease of low pressure of out-
door unit
Pressure ratio is under limit
Outdoor Unit Inverter Compressor CT Sensor open or short
Outdoor Unit Inverter Compressor Discharge Temperature Sensor
open or short
Outdoor Unit Low Pressure Sensor open or short
Outdoor Unit High Pressure Sensor open or short
Outdoor Unit Air Temperature Sensor open or short
Outdoor Unit Heat Exchanger Temperature
Sensor Open or Short
Outdoor Unit Suction Temperature Sensor open or short
Excessive connection of indoor units compared to capacity of outdoor
unit
Failing to receive indoor unit signal at main PCB of outdoor Unit.
Check EEPROM checksum error when resetting power
Restriction of Outdoor Unit Fan
Instant Over Current(Peak) of Outdoor Unit PFC
Liquid pipe temperature sensor of outdoor unit is open or short
Outdoor Unit Subcooling Outlet Temperature Sensor open or short
Pressure unbalance between outdoor units`
Network error of central control unit