Owner’s & Installation Manual 13
ENGLISH
Installation instruction
Function Code
ESP value
ESP step
Press button for 4 seconds
to enter the installer setting
mode until timer segment
display “01:01”.
1
Repeat pressing button to select
Function code 03.
2
Set ESP step by pressing button.
(01: very low, 02: low, 03: medium, 04:
high. 05: power)
3
Move to ESP setting by pressing
button.
4
Press button to select ESP
value(0~255).
5
Installer Setting -E.S.P.
If you set ESP incorrectly, the air conditioner may malfunction.
This setting must be carried out by a certificated-technician.
This function is used for only Duct product.
CAUTION
What is an E.S.P function?
This is the function that decides the strength of the wind for each wind level and because this
function is to make the installation easier, please do not use this function when using the remote
controller.