Specification
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
- 8 -
HP(Equivalent horsepower)
Model Name
Combination Unit
Independent Unit
Capacity Cooling
kW
kcal/h
Btu/h
Heating
kW
kcal/h
Btu/h
Input
Cooling
kW
Heating
kW
Casing Color
Heat Exchanger
Compressor
Type
Piston Displacement
cm
3
/rev
Number of Revolution
R.P.M
Motor Output x Number
W
Starting Method
Oil Type
Oil Charge
cc
Fan
Type
Motor Output x Number
W
Air Flow Rate(High)
CMM
cfm
Drive
Discharge
Side / Top
Pipe Connctions
Liquid Pipes
mm(inch)
Gas Pipes
mm(inch)
Dimensions (WxHxD)
mm
inch
Net Weight
kg
lbs
Transmission Cable
mm
2
Refigerant
Refigerant name
Control
Power Supply
Ø, V, Hz
48
ARUN470DT2
ARUN154DT2
ARUN154DT2
ARUN154DT2
134.4
115,500
458,700
151.2
129,900
516,000
42.00
37.20
Warm Gray
Gold fin
DC Scroll
(52+81.6)*3
(3,600+3,481)*3
(5,356+6,400)x3
Direct On Line
FVC68D(PVE)
5600*3
Propeller fan
350 x 6
570
20,100
DC INVERTER
TOP
19.05(3/4)
41.3(1 5/8)
(1280x1607x730)*3
(50.4x63.3x28.7)*3
285*3
628*3
CVV-SB 1.25x2C
R410A
EEV
3, 460, 60
Heat Pump(460V/60Hz)
Notes:
1. Capacities are based on the following conditions:
Cooling * Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
* Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
* Interconnecting Piping Length 7.5m(24.6ft)
* Level Difference of Zero
Heating * Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
* Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
* Interconnecting Piping Length 7.5m(24.6ft)
* Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. EEV : Electronic Expansion Valve
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
Содержание ARUN076BT2