6. Refrigerant Piping System
13
MULTI V
Modular Heat Pump
Installation Guide
6.2 Indoor Unit Connection
Indoor Unit connecting pipe from branch (a,b,c,d,e,f)
CAUTION
6.3 The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and CF(correction Factor) value
of indoor unit.
Note
• * : For CF value (additional refrigerant) table of indoor units, please refer to PDB of indoor unit.
Indoor Unit capacity [kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
˺
5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8)
Ø15.88(5/8)
• Bending radius should be at least twice the diameter of the pipe.
• Bend pipe after 500mm or more from branch(or header).
Do not bend U type.
It may cause Performance unsatisfactory or noise.
Additional charge(kg)
=
L1(m)
: Total length of
liquid pipe with Ø12.7mm
×
0.118 (kg/m)
Important
Check the Total length between
Heat Exchanger Module ~ Compressor Module ~ Indoor Unit
+
L2(m)
: Total length of
liquid pipe with Ø9.52mm
×
0.061 (kg/m)
+
L3(m)
: Total length of
liquid pipe with Ø6.35mm
×
0.022 (kg/m)
+
CF value of
Heat Exchanger Module (1 kg)
+
CF value of
Indoor unit *
500mm or more
500mm or more
Содержание ARUN050GME0
Страница 1: ...Modular Heat Pump R410A 50Hz 5CVD0 01A P No MFL67474053 ...
Страница 2: ...MULTI V S Modular Heat Pump General information Product Data Installation Guide ...
Страница 3: ...General information MULTI V Modular Heat Pump 1 Model Line up External Appearance 2 Nomenclature ...
Страница 10: ...5 MULTI V Modular Heat Pump Product Data 3 Dimensions 3 1 Dimensional Drawings GG K4 Chassis ARUN050LMC0 ...
Страница 11: ...MULTI V Modular Heat Pump 3 Dimensions 6 Product Data GG B8 Chassis ARUN050GME0 ...
Страница 27: ...22 MULTI V Modular Heat Pump Product Data 10 Wiring Diagrams ARUN050LMC0 ARUN050GME0 ...