PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
39
ENGLISH
Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
≤
5.6(19 100)
Ø 6.35(1/4)
Ø 12.7(1/2)
< 16.0(54 600)
Ø 9.52(3/8)
Ø 15.88(5/8)
≤
22.4(76 400)
Ø 9.52(3/8)
Ø 19.05(3/4)
< 36.4(124 200)
Ø 9.52(3/8)
Ø 22.2(7/8)
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
total capacity(HP)
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
4
Ø 9.52(3/8)
Ø 15.88(5/8)
5
Ø 9.52(3/8)
Ø 15.88(5/8)
6
Ø 9.52(3/8)
Ø 19.05(3/4)
8
Ø 9.52(3/8)
Ø 19.05(3/4)
10
Ø 9.52(3/8)
Ø 22.2(7/8)
12
Ø 12.7(1/2)
Ø 28.58(11/8)