26
ENGLISH
Field Wiring
Single outdoor unit
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Outdoor Unit]
[Indoor Units]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
Outdoor
Power supply
(3Ø 4wires)
Indoor
Power supply
(1
Ø
2wires)
(Main Switch)
HR unit
Master
Outdoor Unit
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
3
4
3
4
3
4
Between Indoor and Master Outdoor unit
The GND terminal at the
main PCB is a ‘-’ terminal
for dry contact, it is not
the point to make ground
connection.
WARNING
• Indoor Unit ground wires are required for preventing electrical
shock accident during current leakage, Communication disorder by
noise effect and motor current leakage (without connection to
pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, mo-
mentary blackout or the power goes on and off while the product is
operating, attach a reversed phase protection circuit locally. Run-
ning the product in reversed phase may break the compressor and
other parts.
!
Frequency
Voltage range(V)
Outdoor
Indoor
60Hz
380V
220V
50Hz
380-415V 220-240V
Series outdoor units
When the power source is connected
In series between the units.
When the power source is supplied to Each outdoor unit individually.
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
[Slave1]
[Slave2]
[Slave3]
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
Outdoor
Power supply
(3Ø 4wires)
Indoor
Power supply
(1Ø 2wires)
(Main Switch)
R S T N
Switch
Fuse
L
N
Communication Line
(2 Wires Cable)
Power Line
(4 Wires Cable)
Communication Line
(3 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
Power Line
(2 Wires Cable)
[Master]
[Indoor Units]
[Slave1]
[Slave2]
[Slave3]
R S T N
Switch
Fuse
R S T N
Switch
Fuse
R S T N
Switch
Fuse
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
HR unit
Outdoor
Power supply
(3Ø 4wires)
Indoor
Power supply
(1Ø 2wires)
(Main Switch)
WARNING
When the total capacity is over than as follow, the power source
do not use in series between the units.
The First terminal block could be burnt out. (Heat Pump : 62 Hp)
!
Frequency
Voltage range(V)
Outdoor
Indoor
60Hz
380V
220V
50Hz
380-415V 220-240V
Frequency
Voltage range(V)
Outdoor
Indoor
60Hz
380V
220V
50Hz
380-415V 220-240V
HR unit
Slave1
Outdoor Unit
Master
Outdoor unit
Slave2
Outdoor Unit
Slave3
Outdoor Unit
3
4
3
4
3
4
Master
Outdoor Unit
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
Between Indoor and Master Outdoor unit
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units
are matched.(A-A,B-B)
WARNING
• Indoor Unit ground wires are required for preventing electrical
shock accident during current leakage, Communication disorder by
noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, mo-
mentary blackout or the power goes on and off while the product is
operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor
and other parts.
!