36
Outdoor Unit
Refrigerant piping installation
◆
The Amount of Refrigerant
The calculation of the additional charge should take account of the length of pipe.
Additional charge (kg)
Product charge(1unit)=8kg
=
+
+
+
+
+
+
=
+
Total liquid pipe (m): Ø22.2mm
x 0.354(kg/m)
x 0.266(kg/m)
x 0.173(kg/m)
x 0.118(kg/m)
x 0.061(kg/m)
x 0.022(kg/m)
Total liquid pipe (m): Ø19.05mm
Total liquid pipe (m): Ø15.88mm
Total liquid pipe (m): Ø12.7mm
Total liquid pipe (m): Ø9.52mm
Total liquid pipe (m): Ø6.35mm
+
x 0.5 kg
Number of installed HR units
CF(kg) (Correction factor)
Total amount(kg)
If a negative result is obtained from
the calculation, no refrigerant needs
to be added.
A
A
B
B
CAUTION
Outdoor unit
HR unit (1EA)
Indoor unit
Ex) 10HP
Additional Charge = A x 0.061 + B x 0.061 + C x 0.061
+ (a+b+c+d+e) x 0.022 + CF
= 40 x 0.061 + 20 x 0.061 + 20 x 0.061
+ (10 x 5) x 0.022 + 0.5(HR)+0(CF)
= 6.48(kg)
A: Ø12.7, 50m
B: Ø9.52, 10m
C: Ø9.52, 10m
D: Ø9.52, 10m
E: Ø6.35, 10m
◆
Special condition
In case of the No. of CST TE/RAC SE/ARTCOOL SF models are over than 50% of the connected
indoor units when the total No. of connected indoor units are over than 50% of the max. connectable
indoor units.
■
Additional refrigerant charging amount (kg) :
= (A x + B x ß) - (AVG x ß)
• A = Total No. of TE,SE and SF Indoor units,
= 0.5
• B = Total No. of except TE,SE and SF Indoor units,
ß = 0.3
• AVG = 50% of Max. No. of connectable Indoor units.
Example)
1) Installation Information
- Outdoor unit : 6HP
- Total indoor units : 6 units (TE 3 units, SE 2 units, BH 1 unit)
2) Information from PDB
- Max. No. of connectable indoor units : 10 units
- Calculated additional refrigerant amount = 2 kg :
3) Indoor refrigerant charging amount
= (5 units x 0.5+1 unit x 0.3) - (5 units x 0.3) = 1.3 kg :
Revised the total additional charging amount =
= 2 kg +1.3 kg
= 3.3 kg
+
=
Total amount(kg)
A
B
+
C