14 Room Air Conditioner
Installation
Piping Length and Elevation
18K
1/2"(Ø12.7)
1/4"(Ø6.35)
24.6ft(7.5m)
49.2ft(15m)
98.4ft(30m)
20
Pipe Size
Capacity
(Btu/h)
GAS
LIQUID
Max.
Length A
Additional
Refrigerant (g/m)
Max.
Elevation B
Standard
Length
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
If piping length is more than 16.4ft(5m)
CAUTION: Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
Oil trap should be installed every 16.4~23 feets (5~7 meters).