ELECTRICAL WIRING
Indoor Unit Electrical Connections
Overview - Connecting Indoor Unit Electrical Wiring
The general guidelines for connecting electrical and communication cables to the indoor unit are the same for each of the Single Zone Wall
Mounted indoor units, however, the actual connections on the terminal block will differ.
•
Be sure that main power to the unit is completely off before proceeding
with these steps. Failure to do so, may cause shock or bodily injury.
•
Follow all safety and warning information outlined at the beginning
and throughout this manual. Failure to do so, may cause bodily injury.
Procedure
Be sure there is no power going through the Single Zone system before
proceeding with these connections as there can be a risk of electrical
shock and bodily injury.
1. The power cord for the Gallery indoor unit is located at the bot-
tom of the unit. See Figure 54.
•
Electrical wiring coming from the outdoor unit will be connected to
this power cord.
•
Pay attention to the location/connection of the green/yellow ground
cable. See Figure 57 on page 51 for proper installation between
the outdoor and indoor unit.
2. Once electrical wiring is completed, refer back to “Front Panel
Assembly/Test Run” on page 43 before running a test on the
system.
3. If all other piping and electrical wiring to the outside unit has been
completed at this stage, you can turn the system on to test.
If you have not completed the piping connections, do not turn power on
at this time as it can result in mechanical failure. Proceed to complete
all other piping, (along with drain hose) and wiring to the system before
running any evaluation testing.
Figure 54: Power Cord at Bottom of Gallery Indoor Unit
•
Follow all safety and warning information outlined at the beginning
and throughout this manual. Failure to do so, may cause unit failure.
•
Some units might require you to remove the Control Cover from the
terminal block area. Most Control Covers are attached with a phillips
screw head.
•
Connect the electrical cable to the indoor unit by connecting the
wires to the terminals on the control board individually according to
the outdoor unit connection. Be sure that the color of the wires at the
outdoor unit along with the terminal numbers are the same as those
for the indoor unit.
Power cord