Service Manual 29
For installation over rated, *a proper quantity of refrigerant should be added for each meter.
Ex) 9K: When installed at a distance of 15m, 148g of
refrigerant should be added.
(15-7.62) x 20g = 148g
INDOOR UNIT
HEAT
EXCHANGER
(EVAPORATOR)
HEAT
EXCHANGER
(CONDENSER)
COMPRESSOR
GAS SIDE
CAPILLARY TUBE
LIQUID SIDE
OUTDOOR UNIT
• Cooling Only Models
MODEL
9K, 12K
(Cooling Only)
Pipe size(Diameter:ø)
Piping length
Elevation
Gas
Liquid
Rated
Max
Rated
Max
1/2"
1/4"
7.62m(25ft)
15m(50ft)
5m(16ft)
7m(23ft)
a proper quantity of refrigerant
9K, 12K
20g
Troubleshooting Guide
Troubleshooting Guide