CONNECTING PIPES
11
ENGLISH
Preparation of Pipe
Main cause of gas leakage is defect in flaring
work. Carry out correct flaring work in the
following procedure.
Cut the pipes and the cable.
- Use the accessory pipe kit or the pipes
purchased locally.
- Measure the distance between the indoor
and the outdoor unit.
- Cut the pipes a longer than measured
distance.
- Cut the cable 1.5 m longer than the pipe
length.
Burrs removal
- Completely remove all burrs from the cut
cross section of pipe.
- Put the end of the copper pipe to downward
direction as you remove burrs in order to
avoid to let burrs drop in the pipe.
Putting nut on
- Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal.
(not possible to put them on after finishing
flare work)
Flaring work
1
Firmly hold copper pipe in a bar with the
dimension shown in below table.
2
Carry out flaring work with the flaring tool.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
CONNECTING PIPES
Pipe diameter
Inch (mm)
A inch (mm)
Wing nut type Clutch type
Ø1/4 (Ø6.35)
0.04~0.07
(1.1~1.8)
0~0.02
(0~0.5)
Ø3/8 (Ø9.52)
Ø1/2 (Ø12.7)
Ø5/8 (Ø15.88)
Flare nut
Copper tube
Bar
Copper pipe
"A"
<Wing nut type>
<Clutch type>