background image

10

Indoor Unit

Installation

Preparation of Piping

1. Cut the pipes and the cable.

Use the accessory piping kit or the pipes purchased
locally.

Measure the distance between the indoor and the out-
door unit.

Cut the pipes a little longer than measured distance.

Cut the cable 1.5m longer than the pipe length.

2. Burrs removal

Completely remove all burrs from the cut cross section
of pipe/tube.

Put the end of the copper tube/pipe to downward direc-
tion as you remove burrs in order to avoid to let burrs
drop in the tubing.

3. Flaring work

Carry out flaring work using flaring tool as shown below.

Firmly hold copper tube in a bar(or die) as indicated
dimension in the table above.

4. Check

Compare the flared work with figure below.

If flare is noted to be defective, cut off the flared section
and do flaring work again.

Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.

Pipe

" A "

Gas

Liquid

Gas

Liquid

<5.6(19,100)

1/2"

1/4"

0.5~0.8

0~0.5

<16.0(54,600)

5/8"

3/8"

0.8~1.0

0.5~0.8

<22.4(76,400)

3/4"

3/8"

1.0~1.3

0.5~0.8

Indoor unit
[kW(Btu/h]

Copper

tube

90

°

Slanted   Uneven  Rough

Pipe

Reamer

Point down

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"A"

Inclined

Inside is shining without scratches.

Smooth all round

Even length

all round

Surface

damaged

Cracked Uneven

thickness

= Improper flaring =

Precautions when connecting pipes
• See the following table for flare part machining dimensions.
• When connecting the flare nuts, apply refrigerant oil to the  inside and outside of the flares and turn them three

or four times at first. (Use ester oil or ether oil.)

• See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
• After all the piping has been connected, use nitrogen to perform a gas leak check.

FLARE SHAPE and FLARE NUT TIGHTENING TORQUE

90

°

±

2

45

°

±

2

A

R=0.4~0.8

pipe size

tightening torque(Ncm)

A(mm)

flare shape

Ø6.35

1400~1600

8.7~9.1

Ø9.5

3270-3990

12.8-13.2

Ø12.7

4950-6030

16.2-16.6

Ø15.9

6180-7540

19.3-19.7

Содержание ARNU18GVJA1

Страница 1: ...ead this installation manual completely before installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH ...

Страница 2: ...eter Flaring tool set Specified torque wrenches different depending on model No Spanner Half union Hexagonal wrench Gas leak detector Vacuum pump Gauge manifold Owner s manual Thermometer Introduction 3 Safety Precautions 4 Installation Selection of the best location7 Preparing Work for Installation 7 Indoor unit Installation 9 Preparation of Piping 10 Checking the Drainage 12 Wiring Connection 12...

Страница 3: ...u to the risk of electric shock This symbol alerts you to hazards that may cause harm to the air conditioner This symbol indicates special notes NOTICE Symbols used in this Manual Features Signal Receptor Drain hose Air Filter Air Discharge Right Side Cover Inlet Grill Left Side Cover ...

Страница 4: ...he possibility of injury or damage to properties only Be sure not to do Be sure to follow the instruction Installation Do not use a defective or under rated circuit breaker Use this appliance on a dedicated circuit There is risk of fire or electric shock For electrical work contact the dealer seller a qualified electri cian or an Authorized Service Center Do not disassemble or repair the product T...

Страница 5: ...l of the case edges and the fins on the condenser and evaporator For installation always contact the dealer or an Authorized Service Center There is risk of fire electric shock explosion or injury Do not install the product on a defective installation stand It may cause injury accident or damage to the product Be sure the installation area does not deteriorate with age If the base collapses the ai...

Страница 6: ...t To avoid vibration or water leakage Do not install the product where the noise or hot air from the out door unit could damage the neighborhoods It may cause a problem for your neighbors Use two or more people to lift and transport the product Avoid personal injury Do not install the product where it will be exposed to sea wind salt spray directly It may cause corrosion on the product Corrosion p...

Страница 7: ...ve two screws from side cover as shown in fig 2 Unlock side cover from side panel by slightly pulling the edge of side cover 3 Tap the side cover with your palm on the back side Inlet grill side 4 Hold the side cover with other hand while tap ping to prevent it to fall down 5 The Drain hole is on the left side of the unit and side cover opening is common for drain pipe connecting pipe and wiring d...

Страница 8: ... of left right back forth by adjusting suspension bolts Adjust a level on the direction of top bottom by adjusting supension bolts Then the unit will be declined to the bottomside so as to drain well Flat washer for M10 accessory Flat washer for M10 accessory Hanging bolt W3 8 or M10 Nut W3 8 or M10 Nut W3 8 or M10 Spring washer M10 5 7mm 3 16 5 16 Indoor WALL Outdoor Suspension bolt B A Washer Nu...

Страница 9: ...g Ceiling Ceiling 10 20mm 5 10mm 1 Install declination of the indoor unit is very important for the drain of the convertible type air conditioner 2 Minimum thickness of the insulation for the connecting pipe shall be 10mm 3 If the Installation Plates are fixed to horizontal line the indoor unit after installing will be declined to the bottomside Front of view The unit must be horizontal or incline...

Страница 10: ...following procedure Pipe A Gas Liquid Gas Liquid 5 6 19 100 1 2 1 4 0 5 0 8 0 0 5 16 0 54 600 5 8 3 8 0 8 1 0 0 5 0 8 22 4 76 400 3 4 3 8 1 0 1 3 0 5 0 8 Indoor unit kW Btu h Copper tube 90 Slanted Uneven Rough Pipe Reamer Point down Bar Copper pipe Clamp handle Red arrow mark Cone Yoke Handle Bar A Inclined Inside is shining without scratches Smooth all round Even length all round Surface damaged...

Страница 11: ...o 4 turns as the initial tightening Opening shutoff valve Closing shutoff valve Shutoff valve size Ø6 4 Ø9 5 Ø12 7 Ø15 9 Ø22 2 Ø25 4 13 5 16 5 18 22 14 17 33 39 50 60 62 75 23 27 13 5 16 5 5 4 6 6 Hexagonal wrench 4mm Hexagonal wrench 6mm Hexagonal wrench 10mm 8 1 9 9 27 33 36 44 11 5 13 9 22 28 Tightening torque N m Turn clockwise to close Shaft valve body Gas line piping attached to unit Cap Val...

Страница 12: ...e following Downward slope Do not raise Accumulated drain water Tip of drain hose dipped in water Air Waving Water leakage Water leakage Ditch Less than 50mm gap Water leakage Terminal Block Indoor 1 L 2 N 3 4 INDOOR POWER INPUT Indoor unit Outdoor unit Central controller A B E F C D Vcc GND Main outdoor unit Connect the wires to the terminals on the control board individually according to the out...

Страница 13: ...ive rise to burn out of the wires 4 Specification of power source 5 Confirm that electrical capacity is sufficient 6 Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate 7 Confirm that the cable thickness is as specified in the power sources specification Particularly note the relation between cable length and thickness 8 Never fail ...

Страница 14: ... as shown in fig 2 Lift slightly the edge of side cover with hands to fix the cover properly on the panel 3 Push the side cover from front side air outlet side towards the inlet grill side to lock the side cover on the main body 4 Fasten the securing screw Cover the Sides Lift the edge with hand ...

Страница 15: ...e room thmperature sensor is in the indoor unit the remote controller should be installed in such places away from direct sunlight and high humidity Installation of the remote controller Select places that are not splashed with water Select controller position after receiving customer approval The room temperature sensor is built in the indoor unit This remote controller equipped with liquid cryst...

Страница 16: ...cover of the wired remote controller to set the mode 2 Select one of three selectable modes as follows Position 1 The room temperature is controlled by the thermistor of the main body Position 2 The room themperature is controlled by the thermis tor of the wired remote controller control the temper ature according to the position of wired remote con troller Position 3 The room temperature is contr...

Отзывы: