8
Indoor Unit
Installation
Terminal Block Indoor
1(L)
2(N)
3
4
A
-
--
-
B
A
B
A
B
GND 12 V
DRY2
DRY1
CEN
Terminal Block of outdoor unit
IDU
(S)ODU
Outdoor Unit
INDOOR
POWER INPUT
• Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit re-
spectively.
Wiring Connection
CAUTION
The connecting cable connected to the indoor and outdoor unit should be complied with the following
specifications (This equipment shall be provided with a cable set complying with the national regula-
tion). If the supply cable is damaged, it must be replaced by a special cable or assembly available
from the manufacturer of its service agent.
WARNING
Make sure that the screws of the terminal are free from looseness.
CAUTION
The Power cord connected to the unit should be selected according to the following specifications.
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit
diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all
tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Confirm the Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 % of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of
a overload protection device.
• Proper starting power is not given to the compressor.
!
!
!
!
※ Resistance measurement position for incorrect wiring.
• Communication and Power Cable
1. Communication Cable : CVV-SB 1.0~1.5x2C
2. Power Cable : CV1.5x3C
Содержание ARNU09GTUB4