Installation Manual 15
ENGLISH
Optional Operation of Wired Remote Controller
Function Code
04:01
Thermistor setting
1. Press
button for 4 seconds to
enter the installer setting mode until
timer segment display “01:01”.
2. Repeat pressing
button to select Function code 04.
3. Set Thermistor mode by pressing
button
(01: Remote Controller,
02: Indoor, 03: 2TH)
4. Press
button to save or release
5. Press
button to exit or system
will automatically exit after 25 seconds
without any input.
❈
Therefore system will use value that sensed from indoor unit or remote controller
❈
If you want to know more Optional Operation, please refer to Wired Remote Controller Manual.
Temperature sensor location
Function
01
Remote controller
Operation in remote controller Temperature sensor
02
Indoor unit
Operation in indoor unit temperature sensor
03
2-Thermistor
Operation in lower temperature after comparing the temperature
between the indoor unit and remote controller
Optional Operation of Wired Remote Controller
Two Thermistor System