Installation
1. Remove the Air Filter.
2. Check the drainage.
• Spray one or two glasses of water upon
the evaporator.
• Ensure that water flows drain hose of
indoor unit without any leakage.
Checking the Drainage
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
n
After all workings are finished, check the working and operation.
• Air distribution ....... Is the air circulation good?
• Drain ..................... Is the drainage smoothly and no sweating?
• Gas leakage ........ Is the piping connection correctly?
• Wiring ................... Is the wiring connection correctly?
• Lock-bolt ............... Is the lock-bolt of compressor loosened?
• Insulation .............. Is the unit fully insulated?
• Ground..................Is the unit safely grounded?
THERMAL INSULATION
Make sure that there is no clearance here.
Overlap with thermal
insulator for piping.
Thermal insulator for refrigerant pipe
(Local supply)
Thermal insulator for
piping(Local supply)
Hose clip for thermal insulator(Local supply)
Felt
Rubber
Insulation
No clearance
Cabinet
Thermal insulator for refrigerant pipe
(Local supply)
Hose clip for thermal insulator
(Local supply)
Union for liquid pipe
Union for gas pipe
Refrigerant pipe and thermalinsulator(Local supply)
TEST AND CHECK
ENGLISH
Installation Manual