56 | GUIDELINES
MUL
TI V Floor
, Suspended, Convertible Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
General Mounting - Ceiling Suspended and Convertible Surface
APPLICATION GUIDELINES
1. Prepare four (4) hanging bolts (each bolt length should be the
same length).
2. Select and mark the areas where the hanging bolts and the piping
access holes should be placed on the ceiling.
3. Drill the holes. Add the washers and regular nuts to the hanging
bolts. Insert the anchor nuts into the ceiling, then firmly mount the
suspension bolts to the anchor nuts.
4. Tighten the washers and regular nuts to lock the hanging bolts to
the ceiling.
5. Secure the hangers on the indoor units to the hanging bolts using
nuts, washers, and spring washers.
6. Measure for level. Adjust the angle as necessary by tightening
and / or loosening the hanging bolts.
7. Adjust the slope by tightening and / or loosening the hanging
bolts. The indoor unit should have a slight incline so it will drain
easily. The incline should be less than or equal to 1°, or between
3/8 - 3/4 inch in drain direction.
General Ceiling Mounting - Ceiling Suspended and Convertible Surface
Indoor Units
Figure 36: Ceiling Mounting for Ceiling Suspended Indoor Units.
Do not damage power wiring during installation. There is risk of elec-
tric shock, which may result in physical injury or death.
Do not damage power wiring during installation. There is a risk of
equipment malfunction, which may result in property damage.
Hanging Bolt
12-5/8
33-11/16
Washer
Nut
Hanging
Bolt
Ceiling
Anchor Nut
Hanging
Bolt
Spring
Washer
Max.
1/2 inch
Hanger
Washer
Nut
Unit: Inch
Suspension Bolt
Piping Hole
Ø1-3/4
9-1/4
2
3-5/16
32-1/4
1-9/16
Washer
Nut
Suspension
Bolt
Ceiling
Anchor Nut
Reference
of Piping
Hole Ø1-3/4
Suspension
Bolt
Spring
Washer
Max.
1/2 inch
Hanger
Washer
Nut
Unit: Inch
Figure 37: Close Up of Hanging Bolt Installation.
Figure 38: Ceiling Mounting for Convertible Surface Indoor Units.
The following are field-supplied:
Flat washer for M10
(accessory)
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)
Spring washer
(M10)
• Hanging bolt - W-3/8 or 1/2
• Nut - W-3/8 or M10
• Spring washer - M10
• Flat washer - M10
• Anchor Nut
The threaded rod hangers (bolts) and hardware must be securely tight-
ened to prevent the unit from falling from its installation location. There is
a risk of personal injury from falling equipment.