LG Control Board Layout
Figure40: Main Module
Drawing
Reference
Terminal
Unit Connection
Type
Position Indicates
Range
2
CH1
CAREL J4 Field Bus Connector
(For Communication with CAREL)
RS485
CH2
RS 485 communication with other Module’s CH1
RS485
CH3
CEN_Bus A&B (To Outdoor Unit)
RS485
CH4
BMS_Bus A&B (To Outdoor Unit)
RS485
3
UI1
Unassigned
0
– 10Vdc
UI2
Outdoor Air Humidity
0
– 10Vdc
0~100%
UI3
Supply Air Temperature (Field Option)
0
– 10Vdc
-146-210F
UI4
Supply Air Relative Humidity (Field Option)
0
– 10Vdc
0~100%
UI5
Differential Pressure Sensor
(For SA flow rate monitoring & CFM Modulation)
0
– 10Vdc
0-
30”wc
UI6
Differential Pressure Sensor (Field Options)
(For EA flow rate monitoring & CFM Modulation)
0
– 10Vdc
UI7
Unassigned
UI8
Space CO
2
Sensor(Field Option)
0
– 10Vdc
0-3000ppm
4
DI1
Forced Stop
NC
(Open = Unit Stop)
DI2
Unit Enable / Disable
NO
(Closed = Unit On)
DI3
Float Switch
NC
(Open = Unit Stop)
5
AO1
Outside Damper output
0
– 10Vdc
0~100%
AO2
Exhaust Damper output
0
– 10Vdc
0~100%
AO3
Recirculation Damper output
0
– 10Vdc
0~100%
AO4
Unassigned
0
– 10Vdc
AO5
Heater_1 (Filed Option)
* Only for Split Compact DOAS
0
– 10Vdc
AO6
Heater_2 (Filed Option)
* Only for Split Compact DOAS
0
– 10Vdc
6
DO1
DO1-COM Error status
C type
NO
(Closed = Alarm)
(C) - COM
NC
(Open = Alarm)
DO2
On / Off Status
NO
(Closed= Unit On
1)
)
DO3
Unassigned
DO4
Unassigned
DO5
Unassigned
DO6
Solenoid Valve (Reheat Coil)
NO
(Closed= Valve open)
Open/Close
1) If fan is running, it indicates as Unit on