background image

- 2 -

Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes

LGE Internal Use Only

1. Specification

Note:

1. Capacities are based on the following conditions:

Cooling: - Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F)

- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F)

Heating: - Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB

- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB

Piping Length - Interconnecting Piping Length 7.5m(24.6 ft.)

- Level Difference of Zero

2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
4. For more Capacity(*),refer to the combination table

Conversion Formula

kW = Btu/h class X 0.0002931

cfm = CMM x 35.3

Power Supply

V, Ø, Hz

Capacity(*)

Btu/h class

Current

Running Current

A

Fan

Motor Type

Fan Type

Motor Output(W) x No. of Unit

Air Flow Rate

CMM

(H / M / L)

CFM

External Static Pressure

mmAq

Capacitor

μF / Vac

Drive

Coil

Row x Column x FPI

Dimensions Body

mm(inch)

(W x H x D)

Decorative Panel

mm(inch)

Net Weight

Body

kg (lbs)

Decorative Panel

kg (lbs)

Sound Level (H / M / L)

dB(A)+3

Piping

Liquid

mm (inch)

Connections

Gas

mm (inch)

Drain(OD/ID)

mm(inch)

Safety Devices

Referigerant

Referigerant Control

Transmission Interunit Cable

No. x AWG

Model

Decoration Panel Name

AMNW07GTRA0[LMCN077HV]

PT-UQC

AMNW09GTRA0[LMCN097HV]

PT-UQC

Indoor unit type

Ceilling Cassette - 4way

208/230, 1, 60

208/230, 1, 60

7,000

9,000

0.25

0.25

BLDC

BLDC

Turbo Fan

Turbo Fan

43 x 1

43 x 1

7.5 / 6.0 / 5.0

8.5 / 7.0 / 6.0

265 / 212 / 177

300 / 265 / 230

-

-

-

-

Direct Drive

Direct Drive

1R x 8C x 18

2R x 8C x 18

570 × 214 × 570 (22-7/16 x 8-7/16 x 22-7/16) 570 × 214 × 570 (22-7/16 x 8-7/16 x 22-7/16)

700 x 22 x 700 (27-9/16 x 7/8 x 27-9/16)

700 x 22 x 700 (27-9/16 x 7/8 x 27-9/16)

14.0 (30.9)

14.0 (30.9)

3.0 (6.6)

3.0 (6.6)

31 / 27 / 24

36 / 33 / 30

6.35 (1/4)

6.35 (1/4)

9.52 (3/8)

9.52 (3/5)

32.0(1-1/4) / 25.0(1)

32.0(1-1/4) / 25.0(1)

Fuse, thermal protector for fan motor Fuse, thermal protector for fan motor

R410A

R410A

EEV(in Outdoor unit)

EEV(in Outdoor unit)

4C x 18

4C x 18

Содержание AMNW07GTRA0

Страница 1: ...ION Before Servicing the unit read the safety precautions in General SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com MODEL AMNW07GTRA0 LMCN077HV AMNW09GTRA0 LMCN097HV AMNW12GTRA0 LMCN125HV AMNW18GTQA0 LMCN185HV ...

Страница 2: ... External Static Pressure mmAq Capacitor μF Vac Drive Coil Row x Column x FPI Dimensions Body mm inch W x H x D Decorative Panel mm inch Net Weight Body kg lbs Decorative Panel kg lbs Sound Level H M L dB A 3 Piping Liquid mm inch Connections Gas mm inch Drain OD ID mm inch Safety Devices Referigerant Referigerant Control Transmission Interunit Cable No x AWG Model Decoration Panel Name AMNW07GTRA...

Страница 3: ...tatic Pressure mmAq Capacitor μF Vac Drive Coil Row x Column x FPI Dimensions Body mm inch W x H x D Decorative Panel mm inch Net Weight Body kg lbs Decorative Panel kg lbs Sound Level H M L dB A 3 Piping Liquid mm inch Connections Gas mm inch Drain OD ID mm inch Safety Devices Referigerant Referigerant Control Transmission Interunit Cable No x AWG Model Decoration Panel Name AMNW12GTRA0 LMCN125HV...

Страница 4: ... exchanger Gas pipe connection port xl are connection Lixuid pipe connection port xl are connection Cooling Heating Turxo x an Th3 Th1 Th2 LOC Description PCB Connector Th1 Thermistor for sunction air temperature CN_ROOM Th2 Thermistor for evaporator inlet temperature CN_PIPE IN Th3 Thermistor for evaporator outlet temperature CN_PIPE OUT ...

Страница 5: ...WER CN POWER CN VANE2 CN VANE2 CN VANE1 CN VANE1 CN DISPLAY CN DISPLAY CN MOTOR1 CN MOTOR1 CN REMO CN REMO CN FLOAT CN FLOAT CN ROOM CN ROOM CN OPTION CN OPTION CN PIPE IN CN PIPE IN CN PIPE OUT CN PIPE OUT CN D PUMP CN POWER CN VANE2 CN VANE1 CN DISPLAY CN MOTOR1 CN VANE1 CN VANE1 CN AIRC CN CC CN REMO CN FLOAT CN ROOM CN PTC CN OPTION CN PIPE IN CN PIPE OUT ...

Страница 6: ...buyer Øs request Please check the correct parts in View RPL Replacement Part List on GCSC GCSC Website http biz Lgservice com 130411 131410 354211 148000 346810 352150 249310 267110 352116 263230B Eva in sensor 263230C Eva out sensor 349600 W49810 330871B W50060 330871A 349480 W3110 359012 W50011 140570 158580 130911B 158591 130911A 249951 268711E 268711C 263230A Air Inlet sensor 135511 266010 352...

Страница 7: ...e check the correct parts in View RPL Replacement Part List on GCSC GCSC Website http biz Lgservice com 130411 131410 148000 346810 352150 249310 267110 352116 263230B Eva in sensor 263230C Eva out sensor 349600 W49810 330871B W50060 330871A 349480 W3110 359012 140570 158580 130911B 158591 130911A 249951 268711E 268711C 263230A Air Inlet sensor 135511 266010 352115 W6640 W51620 18 k Btu h class on...

Страница 8: ...l Accessory Model PT UQC 135316 159830 749740B 749740A 135800 135303 146811 237202 145200 268711 135500 147581 266001 Note Please ensure GCSC since the replacement parts may be changed depending upon the buyer s request Please check the correct parts in View RPL Replacement Part List on GCSC GCSC Website http biz Lgservice com ...

Страница 9: ...P NO MFL61777609 JANUARY 2014 ...

Отзывы: