background image

16

LG Air Conditioners 2013

17

high Static

high Static

B70AWYN983

Note : 1. Due to our policy of innovation some specifications may be changed without notification.

 

2. Capacities are based on the in accordance with ASNZS3823.1.2

    

  Cooling: - Indoor Temperature 27°C DB /19°C WB

                 

- Outdoor Temperature 35°C DB /24°C WB

Heating: - Indoor Temperature 20°C DB / 15°C WB

              - Outdoor Temperature 7°C DB / 6°C WB

B42AWYU3G4 /B55AWYU3G4

Indoor

B42AWYN7G4

B55AWYN7G4

Capacity 

Cooling

Min/Nom/Max

kW

4.9 / 12.3 / 14.8

6.4 / 15.0 / 17.1

Heating

Min/Nom/Max

kW

5.6 / 14.1 / 16.9

7.0 / 17.1 / 18.0

Power Input 

Cooling

Min/Nom/Max

kW

3.65

4.85

Heating

Min/Nom/Max

kW

3.82

5.20 

Running Current 

Cooling/Heating Nom

A

16.0/17.0

21.0/22.7

Power Supply 

V/ø/Hz

220~240 / 1 / 50

220~240 / 1 / 50

EER 

3.37

3.09

COP 

3.69

3.29

Piping Connection

Liquid

mm

ø 9.52

ø 9.52

Gas

mm

ø 15.88

ø 15.88

Drain

O.D./I.D.

mm

ø 32/25

ø 32/25

Air Flow Rate

High/Medium/Low m3/min

48.0 / 42.0 / 36.0

60.0 / 50.0 / 40.0

Sound Pressure

Cooling

High/Medium/Low dBA

46/45/44

46/45/44

Heating

High/Medium/Low dBA

46/45/44

46/45/44

Sound Power

Cooling

Max

dBA

-

-

Dehumidification Rate

l/h

2.7

4.0 

Dimensions

Body

WxHxD

mm

1,320 X 400 X 534

1,320 X 400 X 534

Net Weight

Body

kg

52

52

Supply Air Spigot

WxH

mm

840 X 287

840 X 287

Return Air Spigot

WxH

mm

1,172 X 317

1,172 X 317

Fan Motor Output

W

185 X 2

185 X 2

External Static Pressure-
pre set

Min~Max

mmAq(Pa)

6.35~18.4(62~200)-130

6.35~18.4(62~200)-130

Outdoor

B42AWYU3G4

B55AWYU3G4

Compressor 

Type

Twin Rotary

Twin Rotary

Airflow Rate

Nom

m3/min

55×2

55×2

Sound Pressure

Cooling

Nom

dBA

52

52

Heating

Nom

dBA

54

54

Sound Power

Cooling

Max

dBA

67

71

Dimensions

WxHxD

mm

950 X 1,380 X 330

950 × 1,380 × 330

Net Weight

kg

92.0 

92.0 

Refrigerant

Type

R410A

R410A

Charge

g

3,400

3,400

Chargeless Piping Length (after 7.5m) m

15

15

Operation Range (Outdoor)

Cooling

Min~Max

°C DB

-10 ~ 48

-10 ~ 48

Heating

Min~Max

°C WB

-15 ~ 18

-15 ~ 18

Power Supply

V/ø/Hz

220~240 / 1 / 50

220-240 / 1 / 50

Power Supply Cable

N x mm²

3 x5.0

3 x5.0

Transmission Cable

N x mm²

4 x1.0

4 ×1.0

Circuit Breaker

A

40

40

Piping Length Total

Max

m

50

50

Piping Elevation Difference

IDU-ODU

Max

m

30

30

Piping Connection

Liquid

mm

ø 9.52

ø 9.52

Gas

mm

ø 15.88

ø 15.88

B42AWYN7G4
B55AWYN7G4

B70AWYUX83

Note : 1. Due to our policy of innovation some specifications may be changed without notification.

 

2. Capacities are based on the in accordance with ASNZS3823.1.2

    

  Cooling: - Indoor Temperature 27°C DB /19°C WB

                 

- Outdoor Temperature 35°C DB /24°C WB

Heating: - Indoor Temperature 20°C DB / 15°C WB

              - Outdoor Temperature 7°C DB / 6°C WB

Indoor

B70AWYN983

Capacity 

Cooling

Min/Nom/Max

kW

12.6 / 20.0 / 25.7

Heating

Min/Nom/Max

kW

14.1 / 22.4 / 30.0

Power Input 

Cooling

Min/Nom/Max

kW

3.5/6.47/10.78

Heating

Min/Nom/Max

kW

4.0/6.5910.80

Running Current 

Cooling/Heating Nom

A

10.6/10.7

Power Supply 

V/ø/Hz

220~240 / 1 /50

EER 

3.09

COP 

3.4

Piping Connection

Liquid

mm

ø 9.52

Gas

mm

ø 22.2

Drain

O.D./I.D.

mm

ø 32/25

Air Flow Rate

High/Medium/Low m3/min

70.0 / 65.0 / 60.0

Sound Pressure

Cooling

High/Medium/Low dBA

52/50/49

Heating

High/Medium/Low dBA

52/50/49

Sound Power

Cooling

Max

dBA

-

Dehumidification Rate

l/h

3.67

Dimensions

Body

WxHxD

mm

1,563 X 458 X 791

Net Weight

Body

kg

97

Supply Air Spigot

WxH

mm

1,044 X 286

Return Air Spigot

WxH

mm

1,368 X 392

Fan Motor Output

W

375 X 2

External Static Pressure-
pre set

Min~Max

mmAq(Pa)

6.35~18.4(62~180)-180

Outdoor

B70AWYUX83

Compressor 

Type

INV Scroll

Airflow Rate

Nom

m3/min

190

Sound Pressure

Cooling

Nom

dBA

57

Heating

Nom

dBA

57

Sound Power

Cooling

Max

dBA

78

Dimensions

WxHxD

mm

920 X 1,680 X 760

Net Weight

kg

181.0 

Refrigerant

Type

R410A

Charge

g

6,900

Chargeless Piping Length (after 7.5m) m

15

Operation Range (Outdoor)

Cooling

Min~Max

°C DB

-10 ~ 48

Heating

Min~Max

°C WB

-15 ~ 24

Power Supply

V/ø/Hz

380~415 / 3 / 50

Power Supply Cable

N x mm²

5 x2.5

Transmission Cable

N x mm²

2 x1.0~1.5

Circuit Breaker

A

30

Piping Length Total

Max

m

100

Piping Elevation Difference

IDU-ODU

Max

m

30

Piping Connection

Liquid

mm

ø 9.52

Gas

mm

ø 22.2

Содержание Air Conditioners

Страница 1: ...s Changwon Facility Achieved ISO9001 Certification Under Series 9000 of International Standard Organization ISO Based on Quality Systems For Design Manufacture of Air Conditioners Hermetic Refrication Compressors Australia Pty Ltd Due to LG s policy of continuous improvement and innovation some specifications may change without notice Please check with your retailer AC specialist prior to purchase...

Страница 2: ...2 LG Air Conditioners 2013 3 LG has a comprehensive range of air conditioning solutions designed to suit any sized building or space Enjoy Clean Quiet and Comfortable Air Conditioning with LG ...

Страница 3: ...Indoor _ B70AWYN983 Outdoor_ B70AWYUX83 LG s advanced inverter technology reduces energy consumption and improves running costs Energy Efficiency LG s air conditioning solution allows users to take advantage of a hassle free intuitive management system via the controller User Friendly Control The built in evaporator safety tray makes the product much easier to install and maintain Must be installe...

Страница 4: ...applying Multi V technology Improved cycle efficiency up to 5 with equal distribution The LG BLDC fan motor offers additional efficiency in operating mode up to 40 at low speed 20 at high speed compared to a LG AC motor Powerful BLDC Compressor Heat Exchanger with Wide Louver Fin Optimised Heat Exchanger Path BLDC Fan Motor Technology Heat Exchanger BLDC Fan Motor Technology Powerful BLDC Compress...

Страница 5: ...e LG ducted product you have a choice of 2 convenient options 1 Deluxe Wall Controller 2 Standard wall Controller Deluxe Wall Controller optional LG units come with advanced control options such as the central controller which is designed for commercial applications where multiple units have been installed This allows you control between 16 1024 air conditioning units via 8 seperate controllers Co...

Страница 6: ...Evaporator Safety Tray 2 Split Type Duct Our LG concealed duct models can be installed over a long distance Max 50m and a High Elevation 30m between indoor and outdoor units Long Distance High Elevation Piping Conventional LG Fan and Housing Not available in B70AWYN983 This feature is only available for B70 unit A lightweight polymer blower and housing makes air conditioning operation quieter and ...

Страница 7: ...em Quick Operating Response Wide Operating Range External Static pressure H H M M L L Air volume Air volume can be optimised to reduce noise and comply with the system design utilising E S P technology This enables you to optimise duct work installation by maintaining capacities and sound levels as required E S P Control E S P External Static Pressure Quick Operation Response Wide Operation Range ...

Страница 8: ...ications may be changed without notification 2 Capacities are based on the in accordance with ASNZS3823 1 2 Cooling Indoor Temperature 27 C DB 19 C WB Outdoor Temperature 35 C DB 24 C WB Heating Indoor Temperature 20 C DB 15 C WB Outdoor Temperature 7 C DB 6 C WB B36AWYU4G4 B30AWYU4G4 Indoor B30AWYN7G4 B36AWYN7G4 Capacity Cooling Min Nom Max kW 3 2 8 8 9 6 4 1 9 9 11 0 Heating Min Nom Max kW 3 7 9...

Страница 9: ...r Supply V ø Hz 220 240 1 50 220 240 1 50 Power Supply Cable N x mm 3 x5 0 3 x5 0 Transmission Cable N x mm 4 x1 0 4 1 0 Circuit Breaker A 40 40 Piping Length Total Max m 50 50 Piping Elevation Difference IDU ODU Max m 30 30 Piping Connection Liquid mm ø 9 52 ø 9 52 Gas mm ø 15 88 ø 15 88 B42AWYN7G4 B55AWYN7G4 B70AWYUX83 Note 1 Due to our policy of innovation some specifications may be changed wit...

Страница 10: ...ts Features AC EZ PQCSZ250S0 Provides a centralized point where up to 32 indoor units or indoor unit groups can be controlled and monitored Remote control Monitor 8programmable schedules with mode and set point control Error code display during unit or system malfunction Controller Manual Screw 6EA Screw 4EA LED indicator for operating status Max 32 IDU control AC Smart PQCSW320A1E To control all ...

Страница 11: ...ystem RS485 to LONWORKS Protocol Converter Interface Assembly 12V DC adaptor Manual 64 Indoor units 1BNU LW commission with Web Access can be install with simple central controller Control Method Objective Use Unit Name and Model Function Parts Features BNU BAC PQNFB17B0 To connect PI485 to BACnet BMS system RS485 to BACnet protocol converter Interface Assembly 12V DC adaptor Manual 256 Indoor uni...

Страница 12: ...22 LG Air Conditioners 2013 23 Memo Memo ...