INSTALLATION OF OUTDOOR UNIT
7
ENGLISH
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
More than
300 mm
Fence or
obstacles
More than 700 mm
More than 600 mm
More than
More than
300mm
300mm
More than
300 mm
Sunr
oof
Unit : mm
Installation Places
MODEL
CAPACITY
Pipe Size
Length A (m)
Elevation B (m)
Additional
Refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
AUUQ18GHT0
18 kBtu/h
Ø 12.7(1/2) Ø 6.35(1/4)
7.5
30
5
15
20
AUUW18GHT0
18 kBtu/h
Ø 12.7(1/2) Ø 6.35(1/4)
7.5
50
5
30
20
AUUQ24GHT0
AUUW24GHT0
24 kBtu/h
Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
AUUQ30GHT0
AUUW30GHT0
28 kBtu/h
Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
AUUQ36GHT0
AUUW36GHT0
34 kBtu/h
Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
AUUQ48GHT0
AUUW48GHT0
46 kBtu/h
Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
AUUQ54GHT0
AUUW54GHT0
AUUQ60GHT0
AUUW60GHT0
54 kBtu/h
Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
Free Joint Single Outdoor
Piping length and the elevation
INSTALLATION OF OUTDOOR UNIT