Part 4 Trouble Shooting
- 32 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Code
Contents
Operation
State
Error Display
Cable Remote
Controller
Outdoor Device
Red LED
Green LED
45
Cond. Pipe Sensor Error
Stop
CH45
Flashing
4 times
Flashing
5 times
46
Suction Pipe Sensor Error
Stop
CH46
Flashing
4 times
Flashing
6 times
48
Cond. Out-Pipe Sensor Error
Stop
CH48
Flashing
4 times
Flashing
8 times
51
Over-Capacity Connection Error
Stop
CH51
Flashing
5 times
Flashing
1 time
53
Communication Error between
Outdoor Device
⇔
Indoor Device
Stop
CH53
Flashing
5 times
Flashing
3 times
54
Open and Reverse Phase Error
Stop
CH54
Flashing
5 times
Flashing
4 times
60
EEPROM Check Sum Error
Stop
CH60
Flashing
6 times
-
61
Outdoor Device Pipe Overheating
Error
Stop
CH61
Flashing
6 times
Flashing
1 time
62
Heat-sink Overheating Error
Stop
CH62
Flashing
6 times
Flashing
2 times
65
Heat-sink Sensor Error
Stop
CH65
Flashing
6 times
Flashing
5 times
67
Outdoor BLDC Fan Lock Error
Stop
CH67
Flashing
6 times
Flashing
7 times
71
Converter CT Sensor Error of Outdoor
Unit
Stop
CH71
Flashing
7 times
Flashing
1 time
73
PSC/PFC Over-Current Error (SW)
Stop
CH73
Flashing
7 times
Flashing
3 times
❈
Error checking : The errors may be checked on LED of the display parts of wired remote
controller and the LED of the controller of outdoor device.