14
INSTALLATION INSTRUCTION
ENGLISH
3
Please fix remote controller upper part into
the backplate attached to the surface of
the wall, as the picture below, and then,
connect with backplate by pressing lower
part.
- Please make sure to leave no gaps on the
top, bottom, left or right sides between
the remote controller and backplate.
- Before assembly with the backplate,
arrange the Cable not to interfere with cir-
cuit parts.
Remove remote controller by inserting a
screwdriver into the lower separating holes
and twisting to release the controller from
backplate.
- There are two separating holes. Please in-
dividually separate one at a time.
- Please be careful not to damage the in-
side components when separating.
4
Please refer to the following directions
when connecting the indoor unit and the
wired remote controller together.
- Please connect the cables as shown in
the figure below when connecting the
plug type cable from the indoor unit’s
C/BOX and the housing type of the exten-
sion cable.
- When connecting Terminal Blocks of the
indoor C/BOX and the wired remote con-
troller with the extension cable, refer to
the steps below.
①
Remove the screw on the cable which
is fastened to the wired remote con-
troller’s Terminal Block by loosening
with a screw driver.
②
Remove the housing of the provided 32
ft extension cable with a cutting nipper
and peel it as shown in the figure
below. (when purchasing the extension
cable at the site directly, please peel it
as shown in the figure below.)
Wall
Side
Wall
Side
<Connecting order>
Please check if the connectors
are connected properly.
C/BOX Cable (Plug type)
Extension cable(housing type)
Indoor
Unit side
Wall
Side
Wall
Side
<Separating order>
CAUTION
• Specification of LG supplied extension
cable: AWG#22, 3 core shielded.
(Model : PZCWRC1)
* Apply enclosed noncombustible con-
duit(metal raceway) totally or use FT-6
rated cable or above level in case of local
electric & building code that requires
plenum (CMP) cable usage.
!
1.378 inch(35 mm)
±0.197 inch(5 mm)
0.394 inch(10 mm) ± 0.118 inch(3 mm)
Signal
Yellow
12 V
Red
GND
Black