Refrigerant charge
The calculation of the additional charge should be taken in account for the length of extra pipe.
• Total main pipe(A+B+C) = 30m
• Each branch pipe
a = 10m
b = 8m
c = 5m
d = 3m
e = 10m
❖
Additional Charge
=((30-5) x 50 + (10-5) x 20 + (8-5) x 20
+ (5-5) x 20 + (3-5) x 20 + (10-5) x 20)
- (7-5) x 100 = 1270g
A
Ex) A7UQ406FA1
A
B
C
a
b
c
9k
9k
9k
d
e
9k
■
Multiple Piping Models
■
Distributor type Models
Additional charge (g)
= ((A Room Installation Length – Standard Length ) x 20g/m
+ (B Room Installation Length – Standard Length ) x 20g/m +.. )
- CF(Correction Factor) x 150
❈
CF = Max. number of connectable indoor unit – Total number of connected indoor unit
Additional charge (g)
= (( Total Main piping Length - Main Standard Length ) x 50g/m
+ (A Room Branch Length – Standard Length ) x 20g/m
+ (B Room Branch Length – Standard Length ) x 20g/m
+ (C Room Branch Length – Standard Length ) x 20g/m +.. )
- CF(Correction Factor) x 100
❈
CF = Max. number of connectable indoor unit – Total number of connected indoor unit
9k
Additional Charge Calculation Example-1
Model
Standard
length(m)
Max piping for
one room(m)
Max total Piping
Length(m)
Additional
Charge(g/m)
18
7.5
25
50
20
26
7.5
25
70
20
30
7.5
25
70
20
Multiple Piping Models
Model
Main Piping length
Branch piping length
Standard
length(m)
Additional
refrigerant(g/m)
Standard
length(m)
Additional
refrigerant(g/m)
40
5
50
5
20
48
5
50
5
20
56
5
50
5
20
Distributor type Models
Installation Manual
9
Installation of Indoor, Outdoor Unit