Installation
4.3.2
Measuring battery voltage
Measure the voltage of each battery module.
1. Pull the groove to remove the cover from the
power terminal compartment.
2. Measure the voltage at the terminal block us-
ing a voltmeter. If the voltage is lower than
42 V, do not use the battery module.
3. Replace the cover.
4.4 Connecting communication cables
To enable communication between the battery modules and between the master
module and the higher-level system, connect them to one another using commu-
nication cables.
25
Содержание EM048063P3S
Страница 1: ...48 V Standalone Battery Module Installation Manual ...
Страница 29: ...Installation 4 Connect appropriate power cables between the busbars and the higher level system 29 ...
Страница 34: ...Keep this manual for later use 2017 LG Chem LG Twin Towers 128 Yeoui daero Yeongdeungpo gu Seoul 07336 Korea ...