WARNING:

 

TO AVOID FIRE, SHOCK, OR DEATH; TURN  

 

OFF POWER 

at circuit breaker or fuse and test that power is  

 

off before wiring!

 

 

Preparing and connecting wires:

 

 

Make sure the wires from the wall box are 

straight (cut if  

 

 

necessary)

. Remove insulation from each wall box wire and  

 

 

Sensor Power Base as shown:  

   

Occupancy Sensor Power Base

Cat. No. OPB15

15A @ 120V, 60Hz – Fluorescent/Incandescent 

15A @ 277V, 60Hz – Fluorescent 

3/4 hp @ 120V, 60Hz 

2 hp @ 277V, 60Hz

For use with OSCxx Occupancy Sensors

INSTALLATION INSTRUCTIONS

 

 

Mount power base in desired electrical box   

 

 

application:

 

A.

  

To mount inside 4" octagon 2.125" deep ceiling 

electrical box, refer to Figure 1. Wire per Step 2.

•    Dress line voltage wires to provide enough clearance in electrical 

box when device is installed.

•    Partially thread the two #8-32 screws provided into mounting 

holes of the electrical box.

•    Align the power base body so that it fits between the mounting 

holes of the electrical box and insert over mounting screws.

•    Turn counter clockwise until it reaches the stops.
•    Tighten mounting screws firmly.

 Tools needed to install your Sensor:

Slotted/Phillips Screwdriver 

Pliers  

 

 

 

Cutters 

 

 

 Parts Included List:

Sensor Base (1) 

#8-32 x 3/4" Screw (2) 

#6-32 x 13/16" Screw (2) 

 

FEATURES

•  Adapts OSCxx Sensors to line-voltage 

•   24VDC Output 

•  Mounts inside a 2.125" deep octagon or 4" square  

  Electrical Box (w/mud ring)  

DESCRIPTION

The OPB15 adapts Leviton low-voltage ceiling occupancy sensors 

to operate on line-voltage electrical systems. Designed to control 

up to 15 amps of lighting load from a single occupancy sensor. The 

Power Base contains a power supply and a load switching relay. The 

power supply provides Class II low-voltage power for OSCxx Series 

Occupancy Sensors. The relay in the Power Base is controlled by the 

occupancy sensors connected via the control input of the two-part 

terminal connector. The Power Base includes zero cross switching 

circuitry to minimize inrush current associated with electronic ballasts. 

This reduces wear and tear on the relay contacts making the power 

pack last longer.

Application Notes:

OPB15 works well where installation of a low-voltage wiring typical 

with traditional power packs and sensors is difficult, inconvenient or 

costly. It is ideal for existing buildings where access to wiring is limited 

or for new construction with line-voltage circuiting only.

LOW-VOLTAGE CURRENT CAPACITY

OPB15 is designed for a single occupancy sensor with a maximum 

current capacity of 40mA.

INSTALLING YOUR OCCUPANCY SENSOR POWER 

BASE

NOTE: 

Use check boxes           when Steps are completed. 

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

Step 1

WARNINGS AND CAUTIONS:

•  To be installed and/or used in accordance with appropriate electrical codes and regulations.
•  If you are unsure about any part of these instructions, consult a qualified electrician.
•  Sensors must be mounted on a vibration free surface.

5/8"

(1.6 cm)

Strip Gage (measure bare 

wire here)

Step 3

Step 2

Figure 1 

Ceiling Installation in a 4" Octagon 2.125" Electrical Box

DI-000-OPB15-00A-X3

CATALOG ITEMS

Catalog No.

OPB15-0DW

Power Input

120-277VAC, 60Hz

Power Output

24VDC, 40mA

•  Input voltage tolerance 10% 

•  Output voltage tolerance 15%, Output voltage listed at nominal.

 

 

Wiring your Sensor Power Base (Line Voltage)

:

 

 

NOTE:

 This application is based on the wall box being 

 

 

pre-installed.

 

 

Connect wires per WIRING DIAGRAM as follows: Twist 

 

 

strands of each lead tightly together and, with circuit 

 

 

conductors, push firmly into appropriate wire connector. 

 

 

Screw connectors on clockwise making sure no bare  

 

 

 

conductors show below the wire connectors. 

Step 4

4" Octagon 2.125" Deep Electrical Box

8-32 Screws

Sensor Power Base

Two-Part Terminal

Connector

Ceiling

Sensor

Hot (Black)

Neutral (White)

Load

Black

White

Black

Blue

White

Line 

120/277VAC

 60Hz

Sensor Power

Base

All wires rated at 105° C. 600V insulation. 

Class II wires are Teflon coated.

Signal Name 

           Color                Gauge 

Line Voltage Wires

Line 120/277V 

           Black                14AWG 

Neutral 

           White               14AWG 

Load 

           Blue               14AWG 

Class II Two-Part Terminal

Common 

           Black                  22AWG 

Power (+24VDC) 

            Red                 22AWG 

Control (Occupancy Sensor)  Blue or Gray            22AWG 

WIRE DESIGNATIONS

Step 3 cont’d

WARNINGS AND CAUTIONS:

•  All sensors must be mounted at least 6 feet away from air vents.
•  Disconnect power when servicing fixture or changing lamps.
•  Use this device only with copper or copper clad wire. With aluminum wire use    

  only devices marked CO/ALR or CU/AL.