Leviton Manufacturing Co., Inc.
201 N. Service Rd. Melville, NY 11747-3138 • Tech Line: 1-800-824-3005 • Fax: 1-800-832-9538
© 2013 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
•
www.leviton.com
Photocells
PHOTOCELL PLACEMENT
ODC0P/INDOOR PHOTOCELL MOUNTING LOCATION
ATRIUM PHOTOCELL MOUNTING LOCATION
REFLECTING WALL USING INDOOR SENSOR
SKYLIGHT APPLICATION WITH SKYLIGHT PHOTOCELL
OUTDOOR PHOTOCELL MOUNTED IN 1/2” CONDUIT
Light well - no sconces - indoor photocell
18”
PCIND
PCIND
Light well - with sconces - (UP or UP/DOWN)
Mount photocell in elevation on centerline
of fixture. Do not mount directly in line
with sconces.
Top of photocell should
be level with top of
skylight curb
Photocell in 1/2” conduit.
Photocell must be at
least 12” from side of
skylight and facing up
NOTE:
Support conduit from
unistrut as required
per NEC
UNISTRUT
JUNCTION BOX
1/4” ANGLE
SUPPORT
Sconces
Snow Line
North
Outdoor photocell mounted horizontally on roof or equal,
facing northern sky
Hooded portion on top, pointed away from any nighttime
light sources
60
ODC0P
or PCIND
6-8 FT.
PCATR
Ideal photocell location is in the
middle of the atrium glass pointing
toward the glass