WIRING AND TERMINATION
LumaCAN
TM
is Leviton’s proprietary communication protocol for control
systems. Topology for LumaCAN
TM
is daisy-chain and can only support
home-run configurations when Leviton’s LumaCAN
TM
repeaters catalog
numbers NPRPT-002 and NPRPT-006 are used. LumaCAN
TM
wiring
requires Category 6 or better cable (Leviton Cat. No. WIR06-1K or
equivalent). LumaCAN
TM
requires termination at each end of the
LumaCAN
TM
network.
Installation:
1. Terminate end of network cables to Cat. 6 male plugs using the TIA-
568B pin out shown in Figure 1. When terminating a male Cat. 6 plug to
the network cable hold the plug with the clip down and looking at it from
the back to match the Figure 1.
2. Insert the terminated Cat. 6 plugs in to the ports on the Repeater.
3. Terminate all end-of-line devices.
NOTE: Signal termination required at each end-of-line device. DO
NOT terminate midpoint devices.
2-port repeater: NPRPT-002
• Both ports are internally terminated and this can not be changed.
6-port repeater: NPRPT-006
• Ports B-F are internally terminated and this can not be changed
• Port A: must be terminated if end of run. To terminate, push termination
switch towards Port A. The LumaCAN
TM
"Thru" port should be used if
connecting to another repeater. In this case, the termination switch will
be in the un-terminated position, towards port B. Default configuration
is terminated.