Leviton GreenMAX DRID0-C02 Скачать руководство пользователя страница 2

© 2021 Leviton Mfg. Co., Inc.

FOR CANADA ONLY

For warranty information and/or product returns, residents of Canada should contact Leviton in writing at

 Leviton Manufacturing of 

Canada ULC 

to the attention of the 

Quality Assurance Department

,

165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or 

by telephone at 1 800 405-5320

.

Any changes or modifications not expressly approved by Leviton Manufacturing Co., could void the user’s authority to operate 
the equipment.

FCC Statement:

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC 
Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a 
commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in 
accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a 
residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his  
own expense.

IC Statement:

This device contains license-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development 
Canada’s license-exempt RSS(s). Operation is subject to the following two conditions:
(1) This device may not cause interference.
(2) This device must accept any interference, including interference that may cause undesired operation of the device.

TRADEMARK DISCLAIMER: 

The Leviton word mark and logo and the LumaCAN and GreenMAX trademarks, are the property of Leviton Manufacturing Inc., Co. 
Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes 
only, such use is not meant to imply affiliation, sponsorship, or endorsement.

Specifications

Catalog Nos.

DRID0-C02, DRID0-CB2

Input Voltage/Frequency

+12-24VDC

Input Current

Powered from LumaCAN
45-22mA  + Connected DC Load + Pilot Light Current

Output Voltage

Same as input voltage

Output Current

1.0A Max

IP Rating

00

Terminal Torque Rating, Low Voltage

1.8 lb-in

Network Connections

(2) RJ-45 Cat 6 or better for connection to LumaCAN network. 
Termination provided via local termination jumper.

Network Topology

•  Daisy Chain, 1600 ft. max between repeaters.
•  

Home-Run topology and network length up to 10,000 ft. 
can be achieved when using LumaCAN network repeaters 
(Leviton #NPRPT)

•  Maximum 110 nodes between repeaters
•  Maximum 250 nodes on a LumaCAN network

Operating Temperature

0-45°C

Storage Temperature

-10-70°C

FCC SUPPLIER’S DECLARATION OF CONFORMITY:  

Model DRID0-C02 and DRID0-CB2 are Sold by Leviton Manufacturing Inc. 201 N Service Rd, Melville, NY 11747. 
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause 
harmful interference, and (2) this device must accept any interference received, including interference that may cause  
undesired operation.

1.

  Wire the device and make all network connections. Some examples are shown, but your 

specific situation may warrant slightly different wiring. Refer to your submittal drawings or 
consult factory if you are unclear about connections means and methods.

2.

  Set unique LumaCAN network address (see DIP switch designations below).

3.

   Program the analogue interface using a GreenMAX DRC room controller 

through the GreenMAX DRC System app.

NOTE

Devices are powered from the LumaCAN

TM

 network and power is passed through the AI + 24Vout/

COM terminals. Ensure you have adequate power to power all devices before connecting to the network.

NOTE

LumaCAN network must be powered by Class 2 or LPS power supply and total network power may 

not exceed 1500mA per power segment.

12345678

ON

1

2

4

8

16

32

64

128

Switch Values

ID Address Value = Sum of Switch Values

ID 86 = 2+4+16+64

12345678

ON

ID 2

ID 1

12345678

ON

ID 3

12345678

ON

ID 4

12345678

ON

ID 5

12345678

ON

ID 6

12345678

ON

ID 38

12345678

9

P1

9

9

9

9

9

9

9

10

P2

10

10

10

10

10

10

10

ON

ID 86

Wiring and Network Details

For Technical Assistance Call: 1-800-824-3005 (USA Only) or 1-800-405-5320 (Canada Only) www.leviton.com

  

  

All devices on a LumaCAN network require a unique address. This device supports 
Auto-Addressing which is the preferred method of address assignment.

 • 

 

A GreenMAX DRC Room Controller will assign a unique address to all devices on the 
network. 

 • 

 

For Auto-addressing to work, all dip switches must be set to OFF.

 • 

 

Both AI1/AI2 LED’s will blink when the devices has no address, and, will stop blinking 
when a valid address is assigned.

 • 

 

If you prefer to set an address manually, please use the dip switches to assign a fixed 
address.

LIMITED 5 YEAR WARRANTY AND EXCLUSIONS

Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the 
purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. 

For details visit www.leviton.com or call 1-800-824-3005.

 This warranty excludes and there is disclaimed liability for labor for removal 

of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not 
in accordance with any labels or instructions. 

There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose

, but if any implied warranty is required by the applicable jurisdiction, the 

duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. 

Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage 

to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation

. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

Wiring to a Single Photocell: 

Wiring to a Demand Response Interface: 

Wiring to Switch:

Lum

a

CAN

Common

0-10VDC

+V

Photocell

Com

A1

+V

A2

Internet

Dem

a

nd

Response

Interf

a

ce

Lum

a

CAN

Common

Lo

a

d Shed Trigger

+V

Com

A1

+V

A2

Wiring to (2) Occupancy Zones

:

Lum

a

CAN

Com

A1

+V

A2

Common

Occup

a

ncy Sign

a

l

+V

Zone 1

Occup

a

ncy

Sensor

Zone 2

Occup

a

ncy

Sensor

Occup

a

ncy

Sensor 1

Occup

a

ncy

Sensor 3

Occup

a

ncy

Sensor 2

Wiring to (3) Occupancy Sensors

:

WEB 

VERSION

Отзывы: