Leviton GreenMax  DRID0-C02 Скачать руководство пользователя страница 2

© 2019 Leviton Mfg. Co., Inc.

LIMITED 5 YEAR WARRANTY AND EXCLUSIONS

Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase 
date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. 

For details visit www.leviton.com or call 1-800-824-3005.

 This warranty excludes and there is disclaimed liability for labor for removal of 

this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in 
accordance with any labels or instructions. 

There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose

, but if any implied warranty is required by the applicable jurisdiction, the 

duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. 

Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, 

damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation

. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of 
Canada ULC to the attention of the Quality Assurance Department, 
165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.

FCC AND INDUSTRY CANADA COMPLIANCE STATEMENT

:

FCC & IC Statement - This device complies with Part 15 of the FCC Rules and ISED License-exempt RSS standard(s). Operation 
is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any 
interference received, including interference that may cause undesired operation.  Changes or modifications not expressly approved by 
Leviton could void the user’s authority to operate the equipment.
These limits are designed to provide reasonable protection against harmful interference in a commercial installation. This equipment 
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause 
harmful interference to radio communications. However, there is no guarantee that interference will not occur in a installation. If this 
equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and 
on, the user is encouraged to try to correct the interference by one or more of the following measures: 

- Reorient or relocate the receiving antenna. 
- Increase the separation between the equipment and receiver. 
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. 
- Consult the dealer or an experienced radio/TV technician for help.

This Class A digital apparatus complies with Canadian CAN ICES-3(A)/NMB-3(A).

TRADEMARK DISCLAIMER: 

The Leviton word mark and logo and the LumaCAN and GreenMax trademarks, are the property of 

Leviton Manufacturing Inc., Co. Use herein of third party trademarks, service marks, trade names, brand names and/or product names 
are for informational purposes only, such use is not meant to imply affiliation, sponsorship, or endorsement.

Specifications

Catalog Nos.

DRID0-C02, DRID0-CB2

Input Voltage/Frequency

+12-24VDC

Input Current

Powered from LumaCAN
45-22mA  + Connected DC Load

Output Voltage

Same as input voltage

Output Current

1.5A Max; short circuit current protected/current limited to 
100mA as shipped from factory.  Software Configurable

IP Rating

00

Terminal Torque Rating, Low Voltage

1.8 lb-in

Network Connections

(2) RJ-45 Cat 6 or better for connection to LumaCAN network. 
Termination provided via local termination jumper.

Network Topology

•  Daisy Chain, 1600 ft. max between repeaters.
•  

Home-Run topology and network length up to 10,000 ft. 
can be achieved when using LumaCAN network repeaters 
(Leviton #NPRPT)

•  Maximum 110 nodes between repeaters
•  Maximum 250 nodes on a LumaCAN network

Operating Temperature

0-45°C

Storage Temperature

-10-70°C

FCC SUPPLIER’S DECLARATION OF CONFORMITY:  

Model DRID0-C02 and DRID0-CB2 are Sold by Leviton Manufacturing Inc. 201 N Service Rd, Melville, NY 11747. 

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause 
harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired 
operation.

1.

  Wire the device and make all network connections.  Some examples are shown, but your 

specific situation may warrant slightly different wiring.  Refer to your submittal drawings or 
consult factory if you are unclear about connections means and methods.

Wiring to a Single Photocell: 

Wiring to a Demand Response Interface: 

Wiring to (2) Occupancy Zones

:

2.

  Set unique LumaCAN network address (see DIP switch designations below).

3.

   Program the analogue interface using a GreenMax DRC room controller 

through the GreenMax DRC System app.

NOTE

Devices are powered from the LumaCAN network and power is passed through the AI + 24Vout/COM 

terminals.  Ensure you have adequate power to power all devices before connecting to the network.

NOTE

LumaCAN network must be powered by Class 2 or LPS power supply and total network power may 

not exceed 1500mA per power segment.

Lum

a

CAN

Common

0-10VDC

+V

Photocell

Com

A1

+V

A2

Lum

a

CAN

Common

Occup

a

ncy Sign

a

l

+V

Zone 1

Occup

a

ncy

Sensor

Zone 2

Occup

a

ncy

Sensor

Com

A1

+V

A2

Lum

a

CAN

Common

Lo

a

d Shed Trigger

+V

Internet

Dem

a

nd

Response

Interf

a

ce

Com

A1

+V

A2

12345678

ON

1

2

4

8

16

32

64

128

Switch Values

ID Address Value = Sum of Switch Values

ID 86 = 2+4+16+64

12345678

ON

ID 2

ID 1

12345678

ON

ID 3

12345678

ON

ID 4

12345678

ON

ID 5

12345678

ON

ID 6

12345678

ON

ID 38

12345678

9

P1

9

9

9

9

9

9

9

10

P2

10

10

10

10

10

10

10

ON

ID 86

Wiring and Network Details

 For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com

WEB 

VERSION

Отзывы: