Controller
Twisted Pair
to Power Pack
Power (24VDC) (Green/White)
CAN_H (Blue)
CAN_L (Blue/White)
DC Gnd (Green)
Twisted Pair
to Power Pack
Controller
Power (24VDC)
CAN_H
CAN_L
DC Gnd
Controller
Power (24VDC) (Green/White)
CAN_H (Blue)
CAN_L (Blue/White)
DC Gnd (Green)
To enter Program Mode, push the program button
(use a small screwdriver or pen). In Program Mode,
use the large rocker to cycle programming steps.
Use the small rocker for selection of level or setting.
Press program button to exit Program Mode.
Time
NO
Off
Time
YES
Min
UnOcc
Daylight
Manual
Timeout
Comm.
LED
Address
Wheel
(under frame)
Program
Button
(under
wallplate)
ON - Lights OFF
OFF - Lights ON
MAX
CONTROL
Large Rocker - ON/OFF
Small Rocker - BRIGHT/DIM
Manual Timeout - Selection YES or NO
OFF LED
Service Switch
(pull to engage
- lights remain
OFF while
switch is out)
UnOcc - Selection Min or Off
Large Rocker
Notch
Small Rocker
This side UP when Programming
Brightness Level
Display LED's
Communication
LED
Program
Button
Address
Wheel
Service Switch
ON/OFF LED
1
2
3
4
5
6
7
Figure 3 - Settings
Figure 4 - Program Label
Wiring Diagram 2 - Two Location Application
Wiring Diagram 1 - Single Station Application
DI-000-CN221-00A-Pilot
NOTE: Both Controllers must have
the same address for multiple
location control of 1 Power Pack.
TO OPERATE:
ON: Press the upper half of the large rocker. The lights will fade ON.
OFF: Press the lower half of the large rocker. The lights will fade to OFF (ON/OFF LED lit).
BRIGHTEN:
Press and hold the upper half of the small rocker to the desired light level.
FULL BRIGHT: If the lights ON, pressing the upper half of the large rocker will turn lights ON to the maximum level.
DIM:
sPress and hold the lower half of the small rocker to the desired level.
SERVICE SWITCH: On the lower left corner of the switch plate, there is a Service Switch (refer to Figure 1). When servicing a controlled fixture, pull lever out (OFF
position). This will send a message to the Power Pack to keep the lights OFF. After servicing is complete, push the lever in (ON position) to restore power. The lever must
be pushed in all the way (ON position) for normal operation.
BRIGHTNESS LEVEL DISPLAY: Indicates the level of brightness when the lights are ON. Indicates the previous level of brightness when the lights are OFF (refer to
Figure 2). When lights are OFF, the brightness level of lights can be changed before turning lights ON by pressing the small rocker UP/DOWN.
COMMUNICATION LED: The communication LED will flash when the Controller transmits a message, and when it receives a valid message. It is located under the
wallplate (under the screwless wallplate adapter, not shown) (refer to Figure 3). It is visible in the space between the frame and the wallplate adapter.
LIGHT LEVELS:
MAX: The maximum light level is adjustable between 60%-100%.
MIN: The minimum light level is adjustable between 0%-40%.
UnOccupied: The UnOccupied level is the selection between OFF and MIN. Therefore, when the occupancy sensor detects an absence of motion, the lights will be either
OFF or at MIN, depending on the setting.
Light Maintain: The Light Maintain level is the amount of light that the Power Pack will maintain in the room. The Power Pack maintains a programmed light level by
adjusting the lights automatically to compensate for the ambient light present in the room. If the room is very bright (mid-day), the lights will be set to a dim level. If the
room is dark (evening and morning), the lights will be set to a bright level. This desired level of light is programmed by the Controller.
MANUAL TIME-OUT:
The Power Pack adjusts the lights in order to automatically maintain a programmed light level (as described above). There are times when this light level needs to be
manually overridden. However, some local building codes (such as California Title 24) do not allow lights to be permanently raised above the Light Maintain level. The
time-out is 30 minutes.
NOTE: The time-out can be disabled for installations that do not need to conform to these building codes. The Manual Time-out is a selection between enable (Time YES) and
disable (Time NO).
Power Pack ADDRESS:
The Controller and the Power Pack must have the same address in order to communicate to each other. The default address is the same, but when installing multiple Power Packs,
each must have a different address.
The Controller has an address wheel for addressing (refer to Figure 3). If there is only one Power Pack on the bus, the address wheel DOES NOT have to be adjusted. For
installations where there are multiple Power Packs, the raddress wheel is used to set the Power Pack’s address (refer to the Dimming Power Pack’s Instruction Sheet for
further details).
To set the Power Pack’s address, proceed as follows:
1. Remove wallplate and the frame (may have to remove screwless wallplate adapter also).
2. Using a small screwdriver, rotate the address wheel to the next unused address.
3. Pull out Service Switch.
4. Press the Address Selection button on the Power Pack.
5. Return Service Switch to the IN position.
6. Address is now selected.
NOTE: Only one Power Pack can be programmed at a time.
MULTI-LOCATION:
Up to 4 Controllers can be connected in parallel. All Controllers MUST be on the same address.
COLOR CONVERSION PROCEDURE
The color of this device can be changed to suit your interior design requirements. Simply obtain a color conversion kit of the appropriate color from your Leviton distributor
and proceed as follows (please note that wallplate must be removed).
1. Select the color of the face you desire.
2. The frame has snaps on its sides. Using a small screwdriver, gently remove the frame from the strap (refer to Figure 2).
3. Take the new frame and position it properly to the strap. Notice that the frame has a cut-out for the safety switch lever. Line up the plastic snaps with the square holes
in the strap. Insert the snaps on one side of the frame into the strap.
4. Firmly press sideways and down to slip the other snaps into place. The frame snaps in with a audible click. Ensure that all four snaps are secure. Replace Decora
®
wallplate. The color conversion is complete.
TROUBLESHOOTING
•
If NO LED’s are lit; there is no power
- Check wiring.
•
If none of the Brightness Level Display LED’s are lit, but OFF LED is lit; there is no communication to the Power Pack
- check communication wiring.
- check that Power Pack is operating.
•
Communication LED does NOT light when the button is pressed
- Check power wiring connections.
For Multiple Power Packs on the Bus:
•
The Controller has power (at least the OFF led is ON) but pressing the buttons have no effect on the lights; there is no communication between the Controller and the
Power Pack
- If the communication LED does NOT flash when a button is pressed, see above.
- If the communication LED does flash, check the address of the Power Pack and Controller (refer to Dimming Power Pack Instructions).
To enter Program Mode, push the program button
(use a small screwdriver or pen). In Program Mode,
use the large rocker to cycle programming steps.
Use the small rocker for selection of level or setting.
Press program button to exit Program Mode.
Time
NO
Off
Time
YES
Min
UnOcc
Daylight
Manual
Timeout
Comm.
LED
Address
Wheel
(under frame)
Program
Button
(under
wallplate)
ON - Lights OFF
OFF - Lights ON
MAX
CONTROL
Large Rocker - ON/ OFF
Small Rocker - BRIGHT/DIM
Manual Timeout - Selection YES or NO
OFF LED
Service Switch
(pull to engage
- lights remain
OFF while
switch is out)
UnOcc - Selection Min or Off
This side UP for Programming
Notch
Back of Multi-Gang
Wallplate
DI-000-CN221-00A-Pilot
9/21/01, 4:35 PM
2