Power (24VDC) (Green/White)

CAN_H (Blue)

CAN_L (Blue/White)

DC Gnd (Green)

Twisted Pair

to Power Pack

ON/OFF Controller

Twisted Pair

to Power Pack

Power (24VDC)

CAN_H

CAN_L

DC Gnd

ON/OFF Controller

ON/OFF Controller

Power (24VDC) (Green/White)

CAN_H (Blue)

CAN_L (Blue/White)

DC Gnd (Green)

Communication

LED

Address

Wheel

Service Switch

ON/OFF LED

Figure 3 - Settings

Wiring Diagram 2 - Two Location Application

Wiring Diagram 1 - Single Station Application

NOTE: Both Controllers must have
the same address for multiple
location control of 1 Power Pack.

3. Take the new frame and position it properly to the strap. Notice that the frame has a

cutout for the Service Switch lever. Line up the plastic snaps with the square holes
in the strap. Insert the snaps on one side of the frame into the strap.

4. Firmly press sideways and down to slip the other snaps into place. The frame snaps

in with an audible click. Ensure that all four snaps are secure. Replace Decora

®

wallplate. The color conversion is complete.

TO OPERATE

ON:

Press the upper half of the rocker. The lights will fade ON.

OFF: Press the lower half of the rocker. The lights will fade to OFF (ON/OFF LED lit).

FULL BRIGHT: If the lights ON, pressing the upper half of the rocker will turn lights ON
to the maximum level.

SERVICE SWITCH: On the lower left corner of the switch plate, there is a Service
Switch (refer to Figure 1). When servicing a controlled fixture, pull lever out (OFF
position). This will send a message to the Power Pack to keep the lights OFF. After
servicing is complete, push the lever in (ON position) to restore power. The lever must
be pushed in all the way (ON position) for normal operation.

COMMUNICATION LED: The communication LED will flash when the Controller
transmits a message, and when it receives a valid message. It is located under the
wallplate (under the screwless wallplate adapter, not shown) (refer to Figure 3). It is
visible in the space between the frame and the wallplate adapter.

POWER PACK ADDRESS:

The Controller and the Power Pack must have the same address in order to communi-
cate to each other. The default address is the same, but when installing multiple Power
Packs, each Power Pack must have a different address.

The Controller has a rotary switch for addressing. If there is only one Power Pack on
the bus then the rotary switch DOES NOT have to be adjusted. For installations where
there are multiple Power Packs, the rotary switch is used to set the Power Pack’s
address (refer to the Power Pack Instruction Sheet for further details).

To set the Power Pack’s address, proceed as follows:

1. Remove wallplate and frame (may have to remove screwless wallplate adapter as

well).

2. Using a small screwdriver rotate the rotary switch to next unused address.

3. Pull out Service Switch.

4. Press the Address Selection button on the Power Pack. The Address is now

selected.

5. Return Service Switch to the IN position.

6. Address selection is finished.

NOTE: Only one Power Pack can be programmed at a time.

MULTI-LOCATION:

Up to 4 Controllers can be connected in parallel. All Controllers MUST be on the same
address.

TROUBLESHOOTING

• If the LED is not on; there is no power

- Check wiring.

• Communication LED does NOT light when the button is pressed

- Check power wiring connections.

For Multiple Power Packs on the Bus:

• The Controller has power (the OFF LED is ON) but pressing the buttons have no

effect on the lights; there is no communication between the Controller and the
Power Pack
- If the communication LED does NOT flash when a button is pressed, see above.
- If the communication LED does flash check the address of the Power Pack and
  Controller (refer to Dimming Power Pack Instructions).

DI-000-CN220-00A-Pilot