Leviton 804CP Скачать руководство пользователя страница 4

Page 4

The Leviton 804CP and 808CP represents a key part of a state of the art, total lighting control 

system. Combined with Leviton dimmers and optionally, a Leviton memory control console, a 

totally integrated system is achieved.

The 804CP and 808CP can automatically take control and preset the lighting level of up to 100 

dimmer channels. Control is automatically passed between control panels and the memory 

control console as desired. The 804CP features 4 zone slide controls while the 808CP 

features 8 zone slide control. Both units are exceptionally easy to operate. Remote lockout 

capability is also included. Installation is a snap with the simple 4 wire digital connection

required.

•  Programming differs from other Luma-Net

®

 panels, please read instructions.

• Luma-Net

®

 control panels with software release 3.00 and higher are not directly compatible 

and will not operate with older 400CP panels with software prior to release 3.00. Contact 

dealer or factory for modifications if necessary.

•  Leviton dimming systems used with these release 3.00 panels require the following  

software releases:

  2408CD, 2408CR, 2404CD release 2.30 and above.

  DDS 8600/8800/9600/9800 release 1.30 and above. *

  DDS 6000 release 1.30 and above. *

  DDS 5300/5500/5600 release 1.30 and above. *

  * Optional interface kit required for these units.

WIRING

The 804CP and 808CP will only operate with NSI dimming and control systems explicitly 

designed for interfacing with it. Communication between the panels and the dimming system 

is via a 4 wire interface. Three wires carry the RS 422/485 bi-directional data. A fourth wire 

carries the DC voltage necessary for powering the unit.
Wiring cable between the panels and the dimming system is class 2 and should be at least  

22 AWG, 4 conductor shielded, twisted pairs. (BELDEN 8302, 8723; 22 AWG.) Use 20 AWG 

for runs over 500ft.
The 804CP and 808CP may be connected to the dimming system via parallel or daisy-chained 

wiring. Due to power supply current demands, panels must be limited to 5 units per daisy 

chain run with 22 awg wire, or 10 units with 20 AWG wire.
The Luma-Net

®

 panels feature plug on wiring terminals. The terminals may be unplugged 

from the panel to facilitate ease of wiring and testing. Connect the terminals marked , 

remote-, common, and +15 VDC to the same respective terminals on the dimming system and 

other Luma-Net

®

 panels. Use one twisted pair for and remote- and the other pair for 

common and +15 VDC.
The wiring to the remote lockout switch, if used, can be simple 2 conductor 22 AWG. Connect 

the wires from the switch to the and lockout- terminals. Any panel or group of panels 

may be locked-out remotely by interrupting the +15V supply to the panels. This should not 

affect any other panels still powered, or affect lighting levels currently set.

IMPORTANT: Verify wiring is correct before powering system! Make sure nothing 

conductive may touch pc board or components!

Introduction

Important

Wiring

WEB 

VERSION

Содержание 804CP

Страница 1: ...804CP 808CP Remote Control Panel Installation Operation Guide WEB VERSION ...

Страница 2: ...Page 2 WEB VERSION ...

Страница 3: ...INTRODUCTION 4 IMPORTANT 4 WIRING 4 PROGRAMMING 6 OPERATION 9 Table of Contents WEB VERSION ...

Страница 4: ...nd control systems explicitly designed for interfacing with it Communication between the panels and the dimming system is via a 4 wire interface Three wires carry the RS 422 485 bi directional data A fourth wire carries the DC voltage necessary for powering the unit Wiring cable between the panels and the dimming system is class 2 and should be at least 22 AWG 4 conductor shielded twisted pairs BE...

Страница 5: ...essful reconfiguration of the network If the BUSY LED flashes slowly this indicates a duplicate ID number or wiring problem Program the ID number if not already and observe the BUSY LED Note the busy LED also flashes quickly when the program jumper is removed Now test the dimmer function by operating the panel If the dimmer responds then mount the panel and procede to the next panel in the system and...

Страница 6: ...program the PRESET and ALL OFF buttons easily without additional equipment Other features such as dimmer channel assignment and fade time require a computer and software Details on programming other features are supplied with the Luma Net Software Package Optionally the unit may be ordered preprogrammed from the factory TERMINATION JUMPER PROGRAM JUMPER PROGRAM JUMPER ID NUMBER DIP SWITCH ID NUMBE...

Страница 7: ...network all panels and devices attached except dimmers must have a unique network ID number If two panels have the same network ID number the entire network will stop functioning Panels need not be in program mode to change network ID number since a dipwitch is used To set Network ID number 1 Locate dipswitch on rear of unit as illustrated below 2 Set the switches as per the chart on the following...

Страница 8: ...011100 60 00111100 61 10111100 62 01111100 63 11111100 64 00000010 65 10000010 66 01000010 67 11000010 68 00100010 69 10100010 70 01100010 71 11100010 72 00010010 73 10010010 74 01010010 75 11010010 76 00110010 77 10110010 78 01110010 79 11110010 80 00001010 81 10001010 82 01001010 83 11001010 84 00101010 85 10101010 86 01101010 87 11101010 88 00011010 89 10011010 90 01011010 91 11011010 92 001110...

Страница 9: ...rrent settings of the slide controls All zone LEDs will come on and the slide controls will have full control PRESET button This button will cause all dimmer channels assigned to all zones of this panel to fade to the zone setting previously programmed Default is all full on All zone LEDs will go out ALL OFF button This button will cause all dimmer channels assigned to all zones of this panel to f...

Страница 10: ...Page 10 NOTES WEB VERSION ...

Страница 11: ...Page 11 NOTES WEB VERSION ...

Страница 12: ... normal operating conditions or not in accordance with any labels or instructions There are no other or implied warranties of any kind including merchantability and fitness for a particular purpose but if any implied warranty is required by the applicable jurisdiction the duration of any such implied warranty including merchantability and fitness for a particular purpose is limited to two years Levi...

Отзывы: